Revision as of 01:30, 14 October 2008 editWtshymanski (talk | contribs)Extended confirmed users76,122 edits Flexible Metallic Conduit (FMC): restore text; is this really flex or just armored cable? Not likely to use so much flex in a parking garage.← Previous edit Latest revision as of 03:35, 24 December 2024 edit undoCitation bot (talk | contribs)Bots5,433,271 edits Removed parameters. | Use this bot. Report bugs. | #UCB_CommandLine 
(342 intermediate revisions by more than 100 users not shown)
Line 1: Line 1:
{{Short description|Tube used to protect and route electrical wiring in a building or structure}}
{{commons|Category:Electrical conduit|Electrical conduit}}
] shaft, as seen entering bottom of a ]. The firestop is made of ] on top and ] on the bottom. Raceways are used to protect ]s from damage.]]
]s throughout this highrise ] building ]]
] in a building at Texaco Nanticoke ]]]
{{Electrical Wiring Sidebar}}


An '''electrical conduit''' is a tube used to protect and route ] in a building or structure. Electrical conduit may be made of metal, ], fiber, or ]. Most conduit is rigid, but flexible conduit is used for some purposes.
] shaft, as seen entering bottom of a ]. The firestop is made of ] on top, ] on the bottom. Raceways are used to protect ]s from damage.]]
] throughout this highrise ] ] in ], ].]]
] in a ] at Texaco Nanticoke ] in ], 1980s.]]
].]]
An '''electrical conduit''' is a purpose-designed electrical ] ] used for protection and routing of ]. Electrical conduit may be made of metal, ], fibre, or fired clay. Flexible conduit is available for special purposes.


Conduit is generally installed by ]s at the site of installation of electrical equipment. Its use, form, and installation details are often specified by wiring regulations, such as the U.S. ] or other national or local code. Conduit is generally installed by ]s at the site of installation of electrical equipment. Its use, form, and installation details are often specified by wiring regulations, such as the US ] (NEC) and other ]s.

Early electric lighting installations made use of existing gas pipe to gas light fixtures (converted to electric lamps). Since this technique provided very good protection for interior wiring, it was extended to all types of interior wiring and by the early 20th century purpose-built couplings and fittings were manufactured for electrical use.


==Comparison with other wiring methods== ==Comparison with other wiring methods==
{{unreferenced|section|date=April 2024}}
Electrical conduit provides very good protection to enclosed conductors from impact, moisture, and chemical vapors. Varying numbers, sizes, and types of conductors can be pulled into a conduit, which simplifies design and construction compared to multiple runs of cables or the expense of customized composite cable. Wiring systems in buildings may be subject to frequent alterations. Frequent wiring changes are made simpler and safer through the use of electrical conduit, as existing conductors can be withdrawn and new conductors installed, with little disruption along the path of the conduit.


Electrical conduit provides very good protection to enclosed conductors from impact, moisture, and chemical vapors. Varying numbers, sizes, and types of conductors can be pulled into a conduit, which simplifies design and construction compared to multiple runs of cables or the expense of customised composite cable. Wiring systems in ] are subject to frequent alterations. Frequent wiring changes are made simpler and safer through the use of electrical conduit, as existing conductors can be withdrawn and new conductors installed, with little disruption along the path of the conduit. A conduit system can be made waterproof or submersible. Metal conduit can be used to shield sensitive circuits from electromagnetic interference, and also can prevent emission of such interference from enclosed power cables. A conduit system can be made waterproof or submersible. Metal conduit can be used to shield sensitive circuits from ], and also can prevent emission of such interference from enclosed power cables. Non-metallic conduits resist corrosion and are light-weight, reducing installation labor cost.


When installed with proper sealing fittings, a conduit will not permit the flow of flammable gases and vapors, which provides protection from fire and explosion hazard in areas handling volatile substances. When installed with proper sealing fittings, a conduit will not permit the flow of flammable gases and vapors, which provides protection from fire and explosion hazard in areas handling volatile substances.


Some types of conduit types are approved for direct encasement in concrete. This is commonly used in commercial buildings to allow electrical and communication outlets to be installed in the middle of large open areas. For example, retail display cases and open-office areas use floor-mounted conduit boxes to connect power and communications cables. Some types of conduit are approved for direct encasement in concrete. This is commonly used in commercial buildings to allow electrical and communication outlets to be installed in the middle of large open areas. For example, retail ]s and ] areas use floor-mounted conduit boxes to connect power and communications cables.


Both metal and plastic conduit can be bent at the job site to allow a neat installation without excessive numbers of manufactured fittings. This is particularly advantageous when following irregular or curved building profiles. Both metal and plastic conduit can be bent at the job site to allow a neat installation without excessive numbers of manufactured fittings. This is particularly advantageous when following irregular or curved building profiles. Special ] equipment is used to bend the conduit without kinking or denting it.


The cost of conduit installation is higher than other wiring methods due to the cost of materials and labour. In applications such as residential construction, the high degree of physical damage protection is not required so the expense of conduit is not warranted. Conductors installed within conduit cannot dissipate heat as readily as those installed in open wiring, so the current capacity of each conductor must be reduced (Ampacity Derating) if many are installed in one conduit. It is impractical, and prohibited by wiring regulations, to have more than 360 degrees of total bends in a run of conduit, so special outlet fittings must be provided to allow conductors to be installed without damage in such runs. While metal conduit can be used as a ], the circuit length is limited. A long run of conduit as grounding conductor will not allow proper operation of overcurrent devices on a fault, for example. The cost of conduit installation is higher than other wiring methods due to the cost of materials and labor. In applications such as residential construction, the high degree of physical damage protection may not be required, so the expense of conduit is not warranted. (In certain jurisdictions, such as ], the use of conduit is always required.) Conductors installed within conduit cannot dissipate heat as readily as those installed in open wiring, so the current capacity of each conductor must be reduced (derated) if many are installed in one conduit. It is impractical, and prohibited by wiring regulations, to have more than 360 degrees of total bends in a run of conduit, so special outlet fittings must be provided to allow conductors to be installed without damage in such runs.


Some types of metal conduit may also serve as a useful bonding conductor for grounding (earthing), but wiring regulations may also dictate workmanship standards or supplemental means of grounding for certain types. While metal conduit may sometimes be used as a ], the circuit length is limited. For example, a long run of conduit as grounding conductor may have too high an electrical resistance, and not allow proper operation of overcurrent devices on a fault.
==Types of conduit==


==Types==
Conduit systems are classified by the wall thickness of tubing, mechanical stiffness of the tubing, and material used to make the tubing. Tubing with thicker walls in the same material offers better protection from impact, but increases the weight and cost of the conduit and also increases labor cost to install the system.
Conduit systems are classified by the wall thickness, mechanical stiffness, and material used to make the tubing. Materials may be chosen for mechanical protection, ] resistance, and overall cost of the installation (labor plus material cost). Wiring regulations for ] may require particular types of conduit to be used to provide an approved installation.


===Rigid Metal Conduit (RMC)=== ===Metal===
'''Rigid Metal Conduit''' ('''RMC''') is a thick threaded tubing, usually made of coated steel, though it may be aluminum. Thicker-walled than IMC. '''Rigid metal conduit''' ('''RMC''') is a thick-walled threaded tubing, usually made of coated steel, stainless steel or aluminum.


'''Galvanized rigid conduit''' ('''GRC''') is galvanized steel tubing, with a tubing wall that is thick enough to allow it to be threaded. Its common applications are in commercial and industrial construction.<ref>R.K. Clidero ''Applications of Electrical Construction'', General Publishing Co., Don Mills Ontario Canada, 1975, {{ISBN|0-7736-5011-3}}</ref> It is designed to protect wire and connectors.
===Rigid Nonmetallic Conduit (RNC)===
'''Rigid Nonmetallic Conduit''' ('''RNC''') is a non-metallic unthreaded tubing.


'''Intermediate metal conduit''' ('''IMC''') is a steel tubing heavier than EMT but lighter than RMC. It may be threaded.
===Galvanized rigid conduit (GRC)===
'''Galvanized rigid conduit''' ('''GRC''') is galvanized steel tubing, with a tubing wall that is thick enough to allow it to be threaded. Its common applications are in commercial and industrial construction. <ref> R.K. Clidero ''Applications of Electrical Construction'', General Publishing Co., Don Mills Ontario Canada, 1975, ISBN 0-7736-5011-3 </ref>


'''Electrical metallic tubing''' ('''EMT'''), sometimes called thin-wall, is commonly used instead of galvanized rigid conduit (GRC), as it is less costly and lighter than GRC. EMT itself is not threaded, but can be used with threaded fittings that clamp to it. Lengths of conduit are connected to each other and to equipment with clamp-type fittings. Like GRC, EMT is more common in commercial and industrial buildings than in residential applications. EMT is generally made of coated steel, though it may be aluminum.
===Electrical metallic tubing (EMT)===
'''Electrical metallic tubing''' ('''EMT'''), sometimes called '''thin-wall''', is commonly used instead of galvanised rigid conduit (GRC), as it is less costly and lighter than GRC. EMT is not threaded. Lengths of conduit are connected to each other and to equipment with clamp-type fittings. Like GRC, EMT is more common in commercial and industrial buildings than in residential applications. EMT is generally made of coated steel, though it may be aluminum.


{| class="wikitable"
===Electrical Nonmetallic Tubing (ENT)===
|+ EMT weights and dimensions (])
'''Electrical Nonmetallic Tubing''' ('''ENT''') is a thin-walled corrugated tubing that is moisture-resistant and flame retardant. It is pliable such that it can be bent by hand and is often flexible although the fittings are not. It is not threaded due to its corrugated shape although the fittings might be.
|-
! colspan="2" | EMT sizing
! colspan="2" | Nominal wt. per {{Convert|100|ft|m}}
! colspan="2" | Nominal outside diameter
! colspan="2" | Nominal wall thickness
|-
! US !! Metric !! lb. !! kg !! in. !! mm !! in. !! mm
|-
| 1/2 || 16 || 30 || 13.6 || 0.706 || 17.9 || 0.042 || 1.07
|-
| 3/4 || 21 || 46 || 20.9 || 0.922 || 23.4 || 0.049 || 1.25
|-
| 1 || 27 || 67 || 30.4 || 1.163 || 29.5 || 0.057 || 1.45
|-
| 1 1/4 || 35 || 101 || 45.8 || 1.51 || 38.4 || 0.065 || 1.65
|-
| 1 1/2 || 41 || 116 || 52.6 || 1.74 || 44.2 || 0.065 || 1.65
|-
| 2 || 53 || 148 || 67.1 || 2.197 || 55.8 || 0.065 || 1.65
|-
| 2 1/2 || 63 || 216 || 98 || 2.875 || 73 || 0.072 || 1.83
|-
| 3 || 78 || 263 || 119.3 || 3.5 || 88.9 || 0.072 || 1.83
|-
| 3 1/2 || 91 || 349 || 158.3 || 4 || 101.6 || 0.083 || 2.11
|-
| 4 || 103 || 393 || 178.2 || 4.5 || 114.3 || 0.083 || 2.11
|}


{{Small|EMT is available in trade sizes 1/2" through 4", and 10′ and 20′ lengths.}}
=== Flexible Metallic Conduit (FMC) ===
]
Flexible Metallic Conduit (FMC) is made through the coiling of a self-interlocked ribbed strip of aluminum or steel, forming a hollow tube through which wires can be pulled. FMC is used primarily in dry areas where it would be impractical to install EMT or other non-flexible conduit, yet where metallic strength to protect conductors is still required. The flexible tubing does not maintain any permanent bend.


{{Small|Some manufacturers also produce EMT in a range of colors for easy system identification.}}
Cutting FMC requires a specialized hand tool with a rotary abrasive disc to creates a small incision into the ribbing so that a twisting motion separates the segments. The disc cuts deep enough to sever the armor coil but not so deep that it could damage the inside conductors.


Short segments of FMC called ''whips'' are often used as circuit "pigtails" between fixtures and a ], especially in ]s. Whip assemblies save a great deal of repetitive labor when installations require several pigtails for several fixtures.


'''] conduit''', similar to galvanized steel conduit, is a rigid tube, generally used in commercial and industrial applications where a higher resistance to corrosion is needed. Such locations would include ] plants, where large amounts of ] and cleaning chemicals would make galvanized conduit unsuitable. Aluminum cannot be directly embedded in ], since the metal reacts with the ]s in ]. The conduit may be coated to prevent corrosion by incidental contact with concrete. Aluminum conduit is generally lower cost than steel in addition to having a lower labor cost to install, since a length of aluminum conduit will have about one-third the weight of an equally-sized rigid steel conduit.<ref>{{cite book |publisher=R. S. Means |title=Electrical Cost Data 22nd Edition |isbn=0-87629-504-9 |pages=106–107 table 16 200 Conduits }}</ref>
Flexible metal conduit coated with a UV-resistant polymer is liquid-tight when installed with appropriate ] fittings containing liquid-tight features such as ].


===Non-metal===
Wiring regulations vary; in locales following the U.S. ] (NEC), flexible metallic conduit may serve as an equipment-grounding conductor. Other areas may require a bonding wire for equipment grounding. The bonding wire in direct contact with the interior of the conduit creates a lower resistance grounding conductor than the conduit alone.
]


] conduit has long been considered the lightest in weight compared to steel conduit materials, and usually lower in cost than other forms of conduit.<ref name=Colonial>{{cite web |url=http://outsideplant.colonialteltek.com/Asset/BENEFITS-OF-FIBERGLASS-CONDUIT.pdf |title=Benefits of Fiberglass Conduit |website=All Categories On Colonial Teltek |access-date=2 October 2017 |url-status=live |archive-url=https://web.archive.org/web/20171003075326/http://outsideplant.colonialteltek.com/Asset/BENEFITS-OF-FIBERGLASS-CONDUIT.pdf |archive-date= Oct 3, 2017 }}</ref> In North American electrical practice, it is available in thirteen different size and wall thicknesses,<ref>{{Cite web |last=Ledes |first=Conduit |title=Schedule 40 Conduit Size and Wall Thickness |url=https://www.ledestube.com/wp-content/uploads/2024/08/Schedule-40-PVC-Conduit-Dimensions.pdf |website=Ledestube}}</ref> with the thin-wall variety only suitable for embedded use in concrete, and heavier grades suitable for direct burial and exposed work. Most of the various fittings made for metal conduit are also available in PVC form. The plastic material resists moisture<ref>{{cite web |title=Five advantages of PVC Coated Conduit |url=http://www.flexconduit.com/five-advantages-pvc-coated-conduit/ |website=FlexGlory |date=2016-10-28 |url-status=live |archive-url=https://web.archive.org/web/20231209183435/https://www.flexconduit.com/five-advantages-pvc-coated-conduit/ |archive-date= Dec 9, 2023 }}</ref> and many corrosive substances, but since the tubing is non-conductive an extra bonding (grounding) conductor must be pulled into each conduit. PVC conduit may be heated and bent in the field, by using special heating tools designed for the purpose.
===Liquidtight Flexible Metal Conduit (LFMC)===
'''Liquidtight Flexible Metal Conduit''' ('''LFMC''') is a non-metallic and liquidtight jacket covering a flexible metal interior. The interior is similar to FMC. Originally designed and manufactured by


Joints to fittings are made with slip-on ] connections, which set up rapidly after assembly and attain full strength in about one day. Since slip-fit sections do not need to be rotated during assembly, the special union fittings used with threaded conduit (such as Ericson) are not required. Since PVC conduit has a higher ] than other types, it must be mounted to allow for expansion and contraction of each run. Care should be taken when installing PVC underground in multiple or parallel run configurations due to mutual heating effect of densely packed cables, because the conduit will deform when heated.
===Flexible Metallic Tubing (FMT)===
'''Flexible Metallic Tubing''' ('''FMT''') is a liquidtight metallic tubing but unlike LFMC, it lacks a non-metallic jacket.


'''Reinforced thermosetting resin conduit''' (RTRC) or '''fiberglass conduit'''<ref>{{cite web |url=http://www.ul.com/global/documents/corporate/aboutul/publications/newsletters/electricalconnections/february08.pdf |date=February 2008 |title=Reinforced Thermosetting Resin Conduit: Type RTRC |publisher=Underwriters Labs |access-date=2 October 2017 |url-status=dead |archive-url=https://web.archive.org/web/20171003075449/http://www.ul.com/global/documents/corporate/aboutul/publications/newsletters/electricalconnections/february08.pdf |archive-date= Oct 3, 2017 }}</ref> is light in weight compared to metallic conduits, which contributes to lower labor costs. It is sometimes referred to as FRE which stands for "fiberglass reinforced epoxy", however this term is a legally registered trademark of FRE Composites.<ref>{{Cite web |url=http://trademarks.justia.com/764/41/fre-76441251.html |title=FRE Trademark of FRE COMPOSITES INC. - Registration Number 3043149 - Serial Number 76441251 |website=Justia Trademarks |url-status=live |archive-url=https://web.archive.org/web/20231120051643/https://trademarks.justia.com/764/41/fre-76441251.html |archive-date= Nov 20, 2023 }}</ref> It may also provide lower material cost. RTRC conduit can be used in a variety of indoor and outdoor applications.<ref name="Colonial" /> Fiberglass conduit is available in multiple wall thicknesses to suit various applications and has a support distance very similar to steel. High temperature, low smoke, no flame, classified area (Class I Division 2), and zero halogen versions are also manufactured for specialty applications such as subway tunnels and stations and in the US can meet ] (NFPA) 130 requirements.<ref>{{cite web |url=http://championfiberglass.com/wp-content/uploads/2016/08/DuctCatalog.pdf |title=Champion Duct |website=Champion Fiberglass |access-date=2 October 2017 |url-status=dead |archive-url=https://web.archive.org/web/20171003075612/http://championfiberglass.com/wp-content/uploads/2016/08/DuctCatalog.pdf |archive-date= Oct 3, 2017 }}</ref> Like other non-metallic conduits, a bonding conductor may be required for grounding. Joints are epoxy-glued, which requires some installation labor and time for joints to set. RTRC conduit may not be bent in the field and appropriate fittings must be used to change directions, nor is RTRC conduit approved to support luminaires.
===Liquidtight Flexible Nonmetallic Conduit (LNFC)===
'''Liquidtight Flexible Nonmetallic Conduit''' ('''LNFC''') refers to several types of flame-resistant non-metallic tubing. Interior surfaces may be smooth or corrugated. There may or may not be integral reinforcement within the conduit wall. It is also known as '''FNMC'''.


'''Rigid nonmetallic conduit''' (RNC) is a non-metallic unthreaded smooth-walled tubing.
===Aluminium conduit===


'''Electrical nonmetallic tubing''' (ENT) is a thin-walled corrugated tubing that is moisture-resistant and flame retardant. It is pliable such that it can be bent by hand, and is often flexible although the fittings are not. It is not threaded due to its corrugated shape, although some fittings might be.
] conduit, similar to ] '''M'''etal '''C'''onduit (GMC), is a rigid conduit, generally used in commercial and industrial applications, where a higher resistance to ] is needed. Such locations would include ] plants, where large amounts of ] and cleaning chemicals would make galvanised conduit unsuitable. Aluminium cannot be directly embedded in ], since the metal reacts with the ]s in ]. The conduit may be coated to prevent ] by incidental contact with concrete. The extra cost of aluminium is somewhat offset by the lower labour cost to install, since a length of aluminium conduit will have about one-third the weight of an equally-sized rigid steel conduit.


===Flexible===
===Intermediate metal conduit (IMC)===
]
'''Intermediate Metal Conduit''' ('''IMC''') is a steel tubing heavier than EMT but lighter than RMC. It may be threaded.


Flexible conduits are used to connect to motors or other devices where ] is useful, or where an excessive number of fittings would be needed to use rigid connections. Electrical codes may restrict the length of a run of some types of flexible conduit.
===PVC conduit===
] conduit is the lightest in weight compared to other conduit materials, and usually lower in cost than other forms of conduit. In North American electrical practice, it is available in three different wall thicknesses, with the thin-wall variety only suitable for embedded use in concrete, and heavier grades suitable for direct burial and exposed work. The various fittings made for metal conduit are also made for PVC. The plastic material resists moisture and many corrosive substances, but since the tubing is non-conductive an extra bonding (grounding) conductor must be pulled into each conduit. PVC conduit may be heated and bent in the field. Joints to fittings are made with slip-on solvent-welded connections,which set up rapidly after assembly and attain full strength in about one day. Since slip-fit sections do not need to be rotated during assembly, the special union fittings used with threaded conduit (Ericson) are not required. Since PVC conduit has a higher ] than other types, it must be mounted so as to allow for expansion and contraction of each run. Care should be taken when installing PVC underground in multiple or parallel run configurations due to mutual heating effect of cable


'''Flexible metallic conduit''' ('''FMC''', informally called ''greenfield'' or ''flex'') is made by the ] coiling of a self-interlocked ribbed strip of aluminum or steel, forming a hollow tube through which wires can be pulled. FMC is used primarily in dry areas where it would be impractical to install EMT or other non-flexible conduit, yet where metallic strength to protect conductors is still required. The flexible tubing does not maintain any permanent bend, and can flex freely.
=== Other metal conduits===
In extreme corrosion environments where plastic coating of the tubing is insufficient, conduits may be made from ], ] or ].


FMC may be used as an equipment grounding conductor if specific provisions are met regarding the trade size and length of FMC used, depending on the amperage of the circuits contained in the conduit. In general, an equipment grounding conductor must be pulled through the FMC with an ampacity suitable to carry the fault current likely imposed on the largest circuit contained within the FMC.
===Underground conduit===
<!-- Is this the same as NUCC? -->


'''Liquidtight flexible metal conduit''' ('''LFMC''') is a metallic flexible conduit covered by a waterproof plastic coating. The interior is similar to FMC.
Large diameter (more than 2 inch/50 mm) conduit may be installed underground between buildings to allow installation of power and communication cables. An assembly of these conduits, often called a duct bank, may either be directly buried in earth or encased in concrete. A duct bank will allow replacement of damaged cables between buildings or additional power and communications circuits to be added, without the expense of excavation of a trench. While metal conduit is occasionally used for burial, usually PVC, polyethlyene or polystyrene plastics are now used due to lower cost. Formerly, compressed asbestos fibre mixed with cement was used for some underground installations. Telephone and communications circuits were installed in fired-clay conduit.


'''Flexible metallic tubing''' ('''FMT'''; ]) is not the same as flexible metallic conduit (FMC) which is described in US National Electrical Code (NEC) Article 348. FMT is a raceway, but not a conduit and is described in a separate NEC Article 360. It only comes in 1/2" & 3/4" trade sizes, whereas FMC is sized 1/2" ~ 4" trade sizes. NEC 360.2 describes it as: "A raceway that is circular in cross section, flexible, metallic and liquidtight without a nonmetallic jacket."


'''Liquidtight flexible nonmetallic conduit''' ('''LFNC''') refers to several types of flame-resistant non-metallic tubing. Interior surfaces may be smooth or corrugated. There may be integral reinforcement within the conduit wall. It is also known as FNMC.


===Underground===
<!-- Is this the same as NUCC? -->
Conduit may be installed underground between buildings, structures, or devices to allow installation of power and communication cables. An assembly of these conduits, often called a duct bank, may either be directly buried in earth, or encased in concrete (sometimes with reinforcing ] to aid against ]s). Alternatively, a duct bank may be installed in a ]. A duct bank will allow replacement of damaged cables between buildings or additional power and communications circuits to be added, without the expense of re-excavation of a ]. While metal conduit is occasionally used for burial, usually ], ] or ] plastics are now used due to lower cost, easier installation, and better resistance to ].


Formerly, compressed ] fiber mixed with cement (such as ]) was used for some underground installations. Telephone and communications circuits were typically installed in fired-clay conduit.


===Cost comparison===
==Comparison of some types of conduit==
{| class="wikitable" {| class="wikitable"
|+ Relative to rigid galvanized steel conduit, 3/4 inch (21 metric) size |+ Cost relative to rigid galvanized steel (RGS) conduit, 3/4 inch (21 metric) size
|-
! align=left | Relative
! Type
! align=left | RGS
! Labor
! align=left | Aluminum
! Weight
! align=left | IMC
! Material cost
! align=left | EMT
|-
! align=left | PVC
| RMC

|- valign=top style="border-bottom:1px solid #999;"
| Labor
| 1.0 | 1.0
| 0.89
| 0.89
| 0.62
| 0.55
|- valign=top style="border-bottom:1px solid #999;"
| Weight
| 1.0 | 1.0
| 0.34
| 0.76
| 0.42
| 0.20
|- valign=top style="border-bottom:1px solid #999;"
|Material cost
| 1.0 | 1.0
|-
| Aluminum
| 0.89
| 0.55
| 0.99 | 0.99
|-
| IMC
| 0.89
| 0.76
| 0.84 | 0.84
|-
| EMT
| 0.62
| 0.42
| 0.35 | 0.35
|-
| PVC
| 0.55
| 0.20
| 0.43 | 0.43
|} |}


Exact ratios of installation labor, weight and material cost vary depending on the size of conduit, but the values for 3/4 inch (21 metric) trade size are representative. <ref> John H. Chiang, (Ed), ''RS Means Electrical Cost Data 30th Annual Edition'', RSMeans Construction Publishers, Kingston MA USA, 2007, ISBN 0-87629-856-0 </ref> Exact ratios of installation labor, weight and material cost vary depending on the size of conduit, but the values for 3/4 inch (21 metric) trade size (]) are representative.<ref>John H. Chiang, (Ed), ''RS Means Electrical Cost Data 30th Annual Edition'', RSMeans Construction Publishers, Kingston MA US, 2007, {{ISBN|0-87629-856-0}}</ref>


==Fittings== ==Fittings==
Despite the similarity to pipes used in ], purpose-designed electrical ]s are used to connect conduit.


'''Box connectors''' join conduit to a ] or other electrical box. A typical box connector is inserted into a knockout in a junction box, with the threaded end then being secured with a ring (called a '''lock nut''') from within the box, as a ] would be secured by a nut. The other end of the fitting usually has a ] or compression ring which is tightened down onto the inserted conduit. Fittings for non-threaded conduits are either secured with set screws or with a compression nut that encircles the conduit. Fittings for general purpose use with metal conduits may be made of die-cast zinc, but where stronger fittings are needed, they are made of copper-free aluminum or cast iron.
Despite the similarity to pipes used in ], purpose-designed ]s are used to connect conduit.


'''Couplings''' connect two pieces of conduit together.
''Box connectors'' join conduit to a junction box or other electrical box. A typical box connector is inserted into a knockout in a junction box, with the threaded end then being secured with a ring (called a ''lock nut'') from within the box, as a ] would be secured by a nut. The other end of the fitting usually has a ] or compression ring which is tightened down onto the inserted conduit. Fittings for non-threaded conduits are either secured with set screws or with a compression nut that encircles the conduit. Fittings for general purpose use with metal conduits may be made of die-cast zinc, but where stronger fittings are needed, they are made of copper-free aluminum or cast iron.


Sometimes the fittings are considered sufficiently conductive to ''bond'' (electrically unite) the metal conduit to a metal junction box (thus sharing the box's ground connection); other times, '''grounding bushings''' are used which have ]s from the bushing to a grounding screw on the box.<ref>Cauldwell 2002:109.</ref>
''Couplings'' connect two pieces of conduit together.


Unlike water piping, if the conduit is to be watertight, the idea is to keep water ''out'', not in. In this case, ]s are used with special fittings, such as the ] leading from the overhead ]al ] to the ].
Sometimes the fittings are considered sufficiently conductive to ''bond'' (electrically unite) the metal conduit to a metal junction box (thus sharing the box's ground connection); other times, ''grounding bushings'' are used which have ]s from the bushing to a grounding screw on the box.<ref>Cauldwell 2002:109.</ref>

Unlike water piping, if it the conduit is to be watertight, the idea is to keep water ''out'', not in. In this case, the fittings have ]s, such as the ] leading from the overhead ]al ] to the ].


Flexible metal conduit usually uses fittings with a clamp on the outside of the box, just like bare cables would. Flexible metal conduit usually uses fittings with a clamp on the outside of the box, just like bare cables would.


=== Conduit bodies === === Conduit bodies ===
A '''conduit body''' can be used to provide pulling access in a run of conduit, to allow more bends to be made in a particular section of conduit, to conserve space where a full size bend radius would be impractical or impossible, or to split a conduit path into multiple directions. Conductors may ''not'' be spliced inside a conduit body, unless it is specifically listed for such use.


A ''conduit body'' is used in electrical wiring to enable the installation of ]s (]s) being placed within a conduit. Conduit bodies are different from ]es: a junction box is commonly used to provide space for ] wires, while a conduit body is only used to access wires for pulling. Conduit bodies are also commonly referred to as '''''condulets'''''; "condulet" is a term trademarked by Cooper Crouse-Hinds company. Conduit bodies differ from ]es in that they are not required to be individually supported, which can make them very useful in certain practical applications. Conduit bodies are commonly referred to as '''condulets''', a term trademarked by Cooper Crouse-Hinds company, a division of ].


Conduit bodies come in various types, moisture ratings, and materials, including galvanized steel, aluminum, and PVC. Depending on the material, they use different mechanical methods for securing conduit. Among the types are:
Conduit bodies come in various types and moisture ratings, using different mechanical methods of securing the pipe like conduit to the body: LB, LL, LR are types where the opening is on the back, left and right, respectively. A type T ("Tee") conduit body is like the capital letter of the alphabet — a combination of an LL and LR. The type C (coaxial) conduit body is used to pull conductors in a straight run of conduit or tubing, as it makes no turn between inlet and outlet conduit opening.


*L-shaped bodies ("Ells") include the LB, LL, and LR, where the inlet is in line with the access cover and the outlet is on the back, left and right, respectively. In addition to providing access to wires for pulling, "L" fittings allow a 90 degree turn in conduit where there is insufficient space for a full-radius 90 degree sweep (curved conduit section).
"L" fittings (LB, etc.) are also to enable a 90 degree corner in the conduit where there is insufficient space to mount a full-radius 90 degree sweep (curved conduit section). "Ells" are also frequently used external to a building where a circuit passes through the wall either to underground conduit or up a wall via exterior wiring.
*T-shaped bodies ("Tees") feature an inlet in line with the access cover and outlets to both the cover's left and right.
*C-shaped bodies ("Cees") have identical openings above and below the access cover, and are used to pull conductors in a straight runs as they make no turn between inlet and outlet.
*"Service Ell" bodies (SLBs), shorter ells with inlets flush with the access cover, are frequently used where a circuit passes through an exterior wall from outside to inside.


==Other wireways== ==Other wireways==


===Raceway (wire molding)=== ===Surface mounted raceway (wire molding)===
{{anchor|Raceway}} <!--DAB page ] links here -->
This type of "decorative" conduit is designed to provide an aesthetically acceptable passageway for wiring without hiding it inside or behind a wall. This is used where additional wiring is required, but where going through a wall would be difficult or require ]. The conduit has an open back and is placed over the wire and secured to the surface. ] raceway is often used for ] wiring, such as ] cables in an older ], where it is not practical to ] through ].
This type of "decorative" conduit is designed to provide an aesthetically acceptable passageway for wiring without hiding it inside or behind a wall. This is used where additional wiring is required, but where going through a wall would be difficult or require ]. The conduit has an open face with removable cover, secured to the surface, and wire is placed inside. ] raceway is often used for ] wiring, such as ] cables in an older structure, where it is not practical to ] through ].


;Advantages: ;Advantages:
* It allows one to add new wiring to an existing ] without removing or cutting holes into the ] or ]. * Allows adding new wiring to an existing building without removing or cutting holes into the ], ], concrete, or other wall finish.
* It allows circuits to be easily locatable and accessible for future changes thus enabling minimum effort upgrades. * Allows circuits to be easily locatable and accessible for future changes, thus enabling minimum effort upgrades.

;Disadvantages: ;Disadvantages:
* Its appearance may not be acceptable to all observers. * Appearance may not be acceptable to all observers.


=== Trunking === === Trunking ===
The term ''trunking'' is used in the United Kingdom for electrical wireways, usually made from PVC (for mounting on walls) or metal (for embedding into walls). The term ''trunking'' is used in the United Kingdom for electrical wireways, generally rectangular in cross section with removable lids.


''Mini Trunking'' is a term used in the UK for small form-factor (usually 6mm to 25mm square or rectangle sectioned) PVC wire ways. <ref></ref> ''Mini trunking'' is a term used in the UK for small form-factor (usually 6&nbsp;mm to 25&nbsp;mm square or rectangle sectioned) PVC wireways. In India, this trunking is available with self-fixing tape to ease off installation. <ref>{{cite web|url=https://www.industricals.com/2389853/product/pipes-fittings-cable-trunking/mini-trunking/precision-16-x-16mm-upvc-mini-trunking-ivory|title=Precision 16 x 16mm UPVC Mini Trunking Ivory
|website=Industricals|access-date=12 May 2018}}</ref>


In some countries including Iran, the term 'Trunking' is a channel that allows installation of switches and sockets.
In North American practice "wire trough" or "lay-in wireways" are terms used to designate similar products, but these are never used enclosed in masonry or a wall.


In North American practice, ''wire trough'' and ''lay-in wireways'' are terms used to designate similar products. Wall duct raceway<ref>{{cite web |url=http://www.legrand.us/wiremold/infloor-ducts/ducts/wallduct-medical-raceway-system.aspx#.VC_nARY08mE |title=Wallduct Medical Raceway System |website=Legrand.us|access-date=2014-10-04}}</ref><ref>{{cite web |url=http://www.schneider-electric.com/products/us/en/53900-wire-management/53920-wall-duct/6365-wall-duct/ |title=Wall Duct - Schneider Electric United States|website=Schneider-electric.com|access-date=2014-10-04}}</ref><ref>{{cite web |url=http://www.filgesco.com/RacewaySolutions-Wall.pdf |title=Raceway Solutions - Wall|website=Filgesco.com |access-date=2014-10-04}}</ref><ref>{{cite web |url=http://www.icc.com/c/24/raceway-wall-ducts |title=Raceway & Wiring Ducts |website=Icc.com|access-date=2014-10-04}}</ref> is the term for the type that can be enclosed in a wall.
==Passive fire protection==


===Innerducts===
Conduit is of relevance to both ]ping, where they become ]s, and ], where ] measures can be applied on the outside to keep the internal cables operational during an accidental ]. The British standard BS476 also considers internal fires, whereby the fireproofing must protect the surroundings from cable fires. Any ] must consider the effect upon ampacity derating.
]s are subducts that can be installed in existing underground conduit systems to provide clean, continuous, low-friction paths for placing ]s, which have relatively low pulling tension limits. They provide a means for subdividing conventional conduit that was originally designed for single, large-diameter metallic conductor cables into multiple channels for smaller optical cables.

Innerducts are typically small-diameter, semi-flexible subducts. According to ] GR-356, there are three basic types of innerduct: smoothwall, corrugated, and ribbed.<ref>, Telcordia.</ref> These various designs are based on the profile of the inside and outside diameters of the innerduct. The need for a specific characteristic or combination of characteristics, such as pulling strength, flexibility, or the lowest coefficient of friction, dictates the type of innerduct required.

Beyond the basic profiles or contours (smoothwall, corrugated, or ribbed), innerduct is also available in an increasing variety of multiduct designs. Multiduct may be either a composite unit consisting of up to four or six individual innerducts that are held together by some mechanical means, or a single extruded product having multiple channels through which to pull several cables. In either case, the multiduct is coilable, and can be pulled into existing conduit in a manner similar to that of conventional innerduct.

==Passive fire protection==
{{main|Passive fire protection}}
Conduit is of relevance to both ]ping, where they become ]s, and ], where ] measures can be applied on the outside to keep the internal cables operational during an accidental ]. The ] BS 476 also considers internal fires, whereby the fireproofing must protect the surroundings from cable fires. Any ] must consider the effect upon ampacity derating due to internal heat buildup.


==See also== ==See also==
* ]
<div class="references-small" style="-moz-column-count:3; column-count:3;">
* ] * ]
* ]
* ]
* ]
* ]
* ]
* ]
* ]
* ]
* ]
</div>


==Notes== ==References==
{{Reflist}}
<references/>


==Bibliography== ==Bibliography==
* {{cite book | last=Cauldwell | first=Rex | title=Wiring a House (For Pros By Pros) | publisher=Taunton Press | location=Newtown, CT, USA | year=2002 | id=ISBN 1-56158-527-0 }} * {{cite book | last=Cauldwell | first=Rex | title=Wiring a House (For Pros By Pros) | publisher=Taunton Press | location=Newtown, CT, US | year=2002 | isbn=1-56158-527-0 | url-access=registration | url=https://archive.org/details/isbn_9781561585274 }}


==External links== ==External links==
{{commons category|Electrical conduit}}
*
*
*
*
*



] ]
] ]

]
]

Latest revision as of 03:35, 24 December 2024

Tube used to protect and route electrical wiring in a building or structure
This illustration shows electrical conduit risers, looking up inside a fire-resistance rated shaft, as seen entering bottom of a firestop. The firestop is made of firestop mortar on top and mineral wool on the bottom. Raceways are used to protect electrical cables from damage.
Conduit embedded in concrete structure for distribution of electrical cables throughout this highrise apartment building
Electrical conduit and bus duct in a building at Texaco Nanticoke refinery
Electrical installations
Wiring practice by region or country
Regulation of electrical installations
Cabling and accessories
Switching and protection devices

An electrical conduit is a tube used to protect and route electrical wiring in a building or structure. Electrical conduit may be made of metal, plastic, fiber, or fired clay. Most conduit is rigid, but flexible conduit is used for some purposes.

Conduit is generally installed by electricians at the site of installation of electrical equipment. Its use, form, and installation details are often specified by wiring regulations, such as the US National Electrical Code (NEC) and other building codes.

Comparison with other wiring methods

This section does not cite any sources. Please help improve this section by adding citations to reliable sources. Unsourced material may be challenged and removed.
Find sources: "Electrical conduit" – news · newspapers · books · scholar · JSTOR (April 2024) (Learn how and when to remove this message)

Electrical conduit provides very good protection to enclosed conductors from impact, moisture, and chemical vapors. Varying numbers, sizes, and types of conductors can be pulled into a conduit, which simplifies design and construction compared to multiple runs of cables or the expense of customized composite cable. Wiring systems in buildings may be subject to frequent alterations. Frequent wiring changes are made simpler and safer through the use of electrical conduit, as existing conductors can be withdrawn and new conductors installed, with little disruption along the path of the conduit.

A conduit system can be made waterproof or submersible. Metal conduit can be used to shield sensitive circuits from electromagnetic interference, and also can prevent emission of such interference from enclosed power cables. Non-metallic conduits resist corrosion and are light-weight, reducing installation labor cost.

When installed with proper sealing fittings, a conduit will not permit the flow of flammable gases and vapors, which provides protection from fire and explosion hazard in areas handling volatile substances.

Some types of conduit are approved for direct encasement in concrete. This is commonly used in commercial buildings to allow electrical and communication outlets to be installed in the middle of large open areas. For example, retail display cases and open-office areas use floor-mounted conduit boxes to connect power and communications cables.

Both metal and plastic conduit can be bent at the job site to allow a neat installation without excessive numbers of manufactured fittings. This is particularly advantageous when following irregular or curved building profiles. Special tube bending equipment is used to bend the conduit without kinking or denting it.

The cost of conduit installation is higher than other wiring methods due to the cost of materials and labor. In applications such as residential construction, the high degree of physical damage protection may not be required, so the expense of conduit is not warranted. (In certain jurisdictions, such as Chicago, Illinois, the use of conduit is always required.) Conductors installed within conduit cannot dissipate heat as readily as those installed in open wiring, so the current capacity of each conductor must be reduced (derated) if many are installed in one conduit. It is impractical, and prohibited by wiring regulations, to have more than 360 degrees of total bends in a run of conduit, so special outlet fittings must be provided to allow conductors to be installed without damage in such runs.

Some types of metal conduit may also serve as a useful bonding conductor for grounding (earthing), but wiring regulations may also dictate workmanship standards or supplemental means of grounding for certain types. While metal conduit may sometimes be used as a grounding conductor, the circuit length is limited. For example, a long run of conduit as grounding conductor may have too high an electrical resistance, and not allow proper operation of overcurrent devices on a fault.

Types

Conduit systems are classified by the wall thickness, mechanical stiffness, and material used to make the tubing. Materials may be chosen for mechanical protection, corrosion resistance, and overall cost of the installation (labor plus material cost). Wiring regulations for electrical equipment in hazardous areas may require particular types of conduit to be used to provide an approved installation.

Metal

Rigid metal conduit (RMC) is a thick-walled threaded tubing, usually made of coated steel, stainless steel or aluminum.

Galvanized rigid conduit (GRC) is galvanized steel tubing, with a tubing wall that is thick enough to allow it to be threaded. Its common applications are in commercial and industrial construction. It is designed to protect wire and connectors.

Intermediate metal conduit (IMC) is a steel tubing heavier than EMT but lighter than RMC. It may be threaded.

Electrical metallic tubing (EMT), sometimes called thin-wall, is commonly used instead of galvanized rigid conduit (GRC), as it is less costly and lighter than GRC. EMT itself is not threaded, but can be used with threaded fittings that clamp to it. Lengths of conduit are connected to each other and to equipment with clamp-type fittings. Like GRC, EMT is more common in commercial and industrial buildings than in residential applications. EMT is generally made of coated steel, though it may be aluminum.

EMT weights and dimensions (North America)
EMT sizing Nominal wt. per 100 feet (30 m) Nominal outside diameter Nominal wall thickness
US Metric lb. kg in. mm in. mm
1/2 16 30 13.6 0.706 17.9 0.042 1.07
3/4 21 46 20.9 0.922 23.4 0.049 1.25
1 27 67 30.4 1.163 29.5 0.057 1.45
1 1/4 35 101 45.8 1.51 38.4 0.065 1.65
1 1/2 41 116 52.6 1.74 44.2 0.065 1.65
2 53 148 67.1 2.197 55.8 0.065 1.65
2 1/2 63 216 98 2.875 73 0.072 1.83
3 78 263 119.3 3.5 88.9 0.072 1.83
3 1/2 91 349 158.3 4 101.6 0.083 2.11
4 103 393 178.2 4.5 114.3 0.083 2.11

EMT is available in trade sizes 1/2" through 4", and 10′ and 20′ lengths.

Some manufacturers also produce EMT in a range of colors for easy system identification.


Aluminum conduit, similar to galvanized steel conduit, is a rigid tube, generally used in commercial and industrial applications where a higher resistance to corrosion is needed. Such locations would include food processing plants, where large amounts of water and cleaning chemicals would make galvanized conduit unsuitable. Aluminum cannot be directly embedded in concrete, since the metal reacts with the alkalis in cement. The conduit may be coated to prevent corrosion by incidental contact with concrete. Aluminum conduit is generally lower cost than steel in addition to having a lower labor cost to install, since a length of aluminum conduit will have about one-third the weight of an equally-sized rigid steel conduit.

Non-metal

Plastic tubing for use as electrical conduit

PVC conduit has long been considered the lightest in weight compared to steel conduit materials, and usually lower in cost than other forms of conduit. In North American electrical practice, it is available in thirteen different size and wall thicknesses, with the thin-wall variety only suitable for embedded use in concrete, and heavier grades suitable for direct burial and exposed work. Most of the various fittings made for metal conduit are also available in PVC form. The plastic material resists moisture and many corrosive substances, but since the tubing is non-conductive an extra bonding (grounding) conductor must be pulled into each conduit. PVC conduit may be heated and bent in the field, by using special heating tools designed for the purpose.

Joints to fittings are made with slip-on solvent-welded connections, which set up rapidly after assembly and attain full strength in about one day. Since slip-fit sections do not need to be rotated during assembly, the special union fittings used with threaded conduit (such as Ericson) are not required. Since PVC conduit has a higher coefficient of thermal expansion than other types, it must be mounted to allow for expansion and contraction of each run. Care should be taken when installing PVC underground in multiple or parallel run configurations due to mutual heating effect of densely packed cables, because the conduit will deform when heated.

Reinforced thermosetting resin conduit (RTRC) or fiberglass conduit is light in weight compared to metallic conduits, which contributes to lower labor costs. It is sometimes referred to as FRE which stands for "fiberglass reinforced epoxy", however this term is a legally registered trademark of FRE Composites. It may also provide lower material cost. RTRC conduit can be used in a variety of indoor and outdoor applications. Fiberglass conduit is available in multiple wall thicknesses to suit various applications and has a support distance very similar to steel. High temperature, low smoke, no flame, classified area (Class I Division 2), and zero halogen versions are also manufactured for specialty applications such as subway tunnels and stations and in the US can meet National Fire Protection Association (NFPA) 130 requirements. Like other non-metallic conduits, a bonding conductor may be required for grounding. Joints are epoxy-glued, which requires some installation labor and time for joints to set. RTRC conduit may not be bent in the field and appropriate fittings must be used to change directions, nor is RTRC conduit approved to support luminaires.

Rigid nonmetallic conduit (RNC) is a non-metallic unthreaded smooth-walled tubing.

Electrical nonmetallic tubing (ENT) is a thin-walled corrugated tubing that is moisture-resistant and flame retardant. It is pliable such that it can be bent by hand, and is often flexible although the fittings are not. It is not threaded due to its corrugated shape, although some fittings might be.

Flexible

Flexible metallic conduit used in an underground parking facility

Flexible conduits are used to connect to motors or other devices where isolation from vibration is useful, or where an excessive number of fittings would be needed to use rigid connections. Electrical codes may restrict the length of a run of some types of flexible conduit.

Flexible metallic conduit (FMC, informally called greenfield or flex) is made by the helical coiling of a self-interlocked ribbed strip of aluminum or steel, forming a hollow tube through which wires can be pulled. FMC is used primarily in dry areas where it would be impractical to install EMT or other non-flexible conduit, yet where metallic strength to protect conductors is still required. The flexible tubing does not maintain any permanent bend, and can flex freely.

FMC may be used as an equipment grounding conductor if specific provisions are met regarding the trade size and length of FMC used, depending on the amperage of the circuits contained in the conduit. In general, an equipment grounding conductor must be pulled through the FMC with an ampacity suitable to carry the fault current likely imposed on the largest circuit contained within the FMC.

Liquidtight flexible metal conduit (LFMC) is a metallic flexible conduit covered by a waterproof plastic coating. The interior is similar to FMC.

Flexible metallic tubing (FMT; North America) is not the same as flexible metallic conduit (FMC) which is described in US National Electrical Code (NEC) Article 348. FMT is a raceway, but not a conduit and is described in a separate NEC Article 360. It only comes in 1/2" & 3/4" trade sizes, whereas FMC is sized 1/2" ~ 4" trade sizes. NEC 360.2 describes it as: "A raceway that is circular in cross section, flexible, metallic and liquidtight without a nonmetallic jacket."

Liquidtight flexible nonmetallic conduit (LFNC) refers to several types of flame-resistant non-metallic tubing. Interior surfaces may be smooth or corrugated. There may be integral reinforcement within the conduit wall. It is also known as FNMC.

Underground

Conduit may be installed underground between buildings, structures, or devices to allow installation of power and communication cables. An assembly of these conduits, often called a duct bank, may either be directly buried in earth, or encased in concrete (sometimes with reinforcing rebar to aid against shear forces). Alternatively, a duct bank may be installed in a utility tunnel. A duct bank will allow replacement of damaged cables between buildings or additional power and communications circuits to be added, without the expense of re-excavation of a trench. While metal conduit is occasionally used for burial, usually PVC, polyethylene or polystyrene plastics are now used due to lower cost, easier installation, and better resistance to corrosion.

Formerly, compressed asbestos fiber mixed with cement (such as transite) was used for some underground installations. Telephone and communications circuits were typically installed in fired-clay conduit.

Cost comparison

Cost relative to rigid galvanized steel (RGS) conduit, 3/4 inch (21 metric) size
Type Labor Weight Material cost
RMC 1.0 1.0 1.0
Aluminum 0.89 0.55 0.99
IMC 0.89 0.76 0.84
EMT 0.62 0.42 0.35
PVC 0.55 0.20 0.43

Exact ratios of installation labor, weight and material cost vary depending on the size of conduit, but the values for 3/4 inch (21 metric) trade size (North America) are representative.

Fittings

Despite the similarity to pipes used in plumbing, purpose-designed electrical fittings are used to connect conduit.

Box connectors join conduit to a junction box or other electrical box. A typical box connector is inserted into a knockout in a junction box, with the threaded end then being secured with a ring (called a lock nut) from within the box, as a bolt would be secured by a nut. The other end of the fitting usually has a screw or compression ring which is tightened down onto the inserted conduit. Fittings for non-threaded conduits are either secured with set screws or with a compression nut that encircles the conduit. Fittings for general purpose use with metal conduits may be made of die-cast zinc, but where stronger fittings are needed, they are made of copper-free aluminum or cast iron.

Couplings connect two pieces of conduit together.

Sometimes the fittings are considered sufficiently conductive to bond (electrically unite) the metal conduit to a metal junction box (thus sharing the box's ground connection); other times, grounding bushings are used which have bonding jumpers from the bushing to a grounding screw on the box.

Unlike water piping, if the conduit is to be watertight, the idea is to keep water out, not in. In this case, gaskets are used with special fittings, such as the weatherhead leading from the overhead electrical mains to the electric meter.

Flexible metal conduit usually uses fittings with a clamp on the outside of the box, just like bare cables would.

Conduit bodies

A conduit body can be used to provide pulling access in a run of conduit, to allow more bends to be made in a particular section of conduit, to conserve space where a full size bend radius would be impractical or impossible, or to split a conduit path into multiple directions. Conductors may not be spliced inside a conduit body, unless it is specifically listed for such use.

Conduit bodies differ from junction boxes in that they are not required to be individually supported, which can make them very useful in certain practical applications. Conduit bodies are commonly referred to as condulets, a term trademarked by Cooper Crouse-Hinds company, a division of Cooper Industries.

Conduit bodies come in various types, moisture ratings, and materials, including galvanized steel, aluminum, and PVC. Depending on the material, they use different mechanical methods for securing conduit. Among the types are:

  • L-shaped bodies ("Ells") include the LB, LL, and LR, where the inlet is in line with the access cover and the outlet is on the back, left and right, respectively. In addition to providing access to wires for pulling, "L" fittings allow a 90 degree turn in conduit where there is insufficient space for a full-radius 90 degree sweep (curved conduit section).
  • T-shaped bodies ("Tees") feature an inlet in line with the access cover and outlets to both the cover's left and right.
  • C-shaped bodies ("Cees") have identical openings above and below the access cover, and are used to pull conductors in a straight runs as they make no turn between inlet and outlet.
  • "Service Ell" bodies (SLBs), shorter ells with inlets flush with the access cover, are frequently used where a circuit passes through an exterior wall from outside to inside.

Other wireways

Surface mounted raceway (wire molding)

This type of "decorative" conduit is designed to provide an aesthetically acceptable passageway for wiring without hiding it inside or behind a wall. This is used where additional wiring is required, but where going through a wall would be difficult or require remodeling. The conduit has an open face with removable cover, secured to the surface, and wire is placed inside. Plastic raceway is often used for telecommunication wiring, such as network cables in an older structure, where it is not practical to drill through concrete block.

Advantages
  • Allows adding new wiring to an existing building without removing or cutting holes into the drywall, lath and plaster, concrete, or other wall finish.
  • Allows circuits to be easily locatable and accessible for future changes, thus enabling minimum effort upgrades.
Disadvantages
  • Appearance may not be acceptable to all observers.

Trunking

The term trunking is used in the United Kingdom for electrical wireways, generally rectangular in cross section with removable lids.

Mini trunking is a term used in the UK for small form-factor (usually 6 mm to 25 mm square or rectangle sectioned) PVC wireways. In India, this trunking is available with self-fixing tape to ease off installation.

In some countries including Iran, the term 'Trunking' is a channel that allows installation of switches and sockets.

In North American practice, wire trough and lay-in wireways are terms used to designate similar products. Wall duct raceway is the term for the type that can be enclosed in a wall.

Innerducts

Innerducts are subducts that can be installed in existing underground conduit systems to provide clean, continuous, low-friction paths for placing optical cables, which have relatively low pulling tension limits. They provide a means for subdividing conventional conduit that was originally designed for single, large-diameter metallic conductor cables into multiple channels for smaller optical cables.

Innerducts are typically small-diameter, semi-flexible subducts. According to Telcordia GR-356, there are three basic types of innerduct: smoothwall, corrugated, and ribbed. These various designs are based on the profile of the inside and outside diameters of the innerduct. The need for a specific characteristic or combination of characteristics, such as pulling strength, flexibility, or the lowest coefficient of friction, dictates the type of innerduct required.

Beyond the basic profiles or contours (smoothwall, corrugated, or ribbed), innerduct is also available in an increasing variety of multiduct designs. Multiduct may be either a composite unit consisting of up to four or six individual innerducts that are held together by some mechanical means, or a single extruded product having multiple channels through which to pull several cables. In either case, the multiduct is coilable, and can be pulled into existing conduit in a manner similar to that of conventional innerduct.

Passive fire protection

Main article: Passive fire protection

Conduit is of relevance to both firestopping, where they become penetrants, and fireproofing, where circuit integrity measures can be applied on the outside to keep the internal cables operational during an accidental fire. The British standard BS 476 also considers internal fires, whereby the fireproofing must protect the surroundings from cable fires. Any external treatments must consider the effect upon ampacity derating due to internal heat buildup.

See also

References

  1. R.K. Clidero Applications of Electrical Construction, General Publishing Co., Don Mills Ontario Canada, 1975, ISBN 0-7736-5011-3
  2. Electrical Cost Data 22nd Edition. R. S. Means. pp. 106–107 table 16 200 Conduits. ISBN 0-87629-504-9.
  3. ^ "Benefits of Fiberglass Conduit" (PDF). All Categories On Colonial Teltek. Archived (PDF) from the original on Oct 3, 2017. Retrieved 2 October 2017.
  4. Ledes, Conduit. "Schedule 40 Conduit Size and Wall Thickness" (PDF). Ledestube.
  5. "Five advantages of PVC Coated Conduit". FlexGlory. 2016-10-28. Archived from the original on Dec 9, 2023.
  6. "Reinforced Thermosetting Resin Conduit: Type RTRC" (PDF). Underwriters Labs. February 2008. Archived from the original (PDF) on Oct 3, 2017. Retrieved 2 October 2017.
  7. "FRE Trademark of FRE COMPOSITES INC. - Registration Number 3043149 - Serial Number 76441251". Justia Trademarks. Archived from the original on Nov 20, 2023.
  8. "Champion Duct" (PDF). Champion Fiberglass. Archived from the original (PDF) on Oct 3, 2017. Retrieved 2 October 2017.
  9. John H. Chiang, (Ed), RS Means Electrical Cost Data 30th Annual Edition, RSMeans Construction Publishers, Kingston MA US, 2007, ISBN 0-87629-856-0
  10. Cauldwell 2002:109.
  11. "Precision 16 x 16mm UPVC Mini Trunking Ivory". Industricals. Retrieved 12 May 2018.
  12. "Wallduct Medical Raceway System". Legrand.us. Retrieved 2014-10-04.
  13. "Wall Duct - Schneider Electric United States". Schneider-electric.com. Retrieved 2014-10-04.
  14. "Raceway Solutions - Wall" (PDF). Filgesco.com. Retrieved 2014-10-04.
  15. "Raceway & Wiring Ducts". Icc.com. Retrieved 2014-10-04.
  16. GR-356, Generic Requirements for Optical Cable Innerduct, Associated Conduit, and Accessories, Telcordia.

Bibliography

External links

Categories: