Revision as of 18:26, 18 March 2013 editWtshymanski (talk | contribs)Extended confirmed users76,122 edits if this is what you need the minus sign for, don't need 12 bogo refs; say what you mean concisely.← Previous edit | Latest revision as of 09:54, 15 December 2024 edit undoNewton-second (talk | contribs)191 edits Improve equation for general case computation.Tag: Visual edit | ||
(611 intermediate revisions by more than 100 users not shown) | |||
Line 1: | Line 1: | ||
{{Short description|Ratio of active power to apparent power}} | |||
{{other uses|Power factor (pistol)}} | |||
{{For|the firearms cartridge ranking system|Power factor (shooting sports)}} | |||
The '''power factor''' of an ] electrical power system is defined as the ] of the ] flowing to the ], to the ] in the circuit,<ref>''IEEE Std. 100 Authoritative Dictionary of Standards Terms, 7th edition''ISBN 0-7381-2601-2</ref><ref>''IEEE Std. 1459-2000 Trial-Use Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions'', Institute of Electrical and Electronics Engineers Inc., 2000, 0-7381-1963-6. This standard says in Note 1, section 3.1.1.1 when defining the quantities for power factor, that real power only flows to the load and can never be negative</ref> and is a ] between 0 and 1. Negative values displayed on some instruments indicate reverse power flow. | |||
In ], the '''power factor''' of an ] system is defined as the ] of the '']'' absorbed by the ] to the '']'' flowing in the circuit. Real power is the average of the instantaneous product of voltage and current and represents the capacity of the electricity for performing work. Apparent power is the product of ] (RMS) current and voltage. Due to energy stored in the load and returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn from the source, the apparent power may be greater than the real power, so more current flows in the circuit than would be required to transfer real power alone. A power factor magnitude of less than one indicates the voltage and current are not in phase, reducing the average ] of the two. A negative power factor occurs when the device (normally the load) generates real power, which then flows back towards the source. | |||
In an electric power system, a load with a low power factor draws more current than a load with a high power factor for the same amount of useful power transferred. The larger currents increase the energy lost in the distribution system and require larger wires and other equipment. Because of the costs of larger equipment and wasted energy, electrical utilities will usually charge a higher cost to industrial or commercial customers with a low power factor. | |||
Linear loads with low power factor (such as ]s) can be corrected with a passive network of ]s or ]s. Non-linear loads, such as ]s, distort the current drawn from the system. In such cases, active or passive power factor correction may be used to counteract the distortion and raise the power factor. The devices for correction of the power factor may be at a central substation, spread out over a distribution system, or built into power-consuming equipment. | |||
'''Power-factor correction''' increases the power factor of a load, improving efficiency for the distribution system to which it is attached. Linear loads with a low power factor (such as ]s) can be corrected with a passive network of ]s or ]s. Non-linear loads, such as ]s, distort the current drawn from the system. In such cases, active or passive power factor correction may be used to counteract the distortion and raise the power factor. The devices for correction of the power factor may be at a central ], spread out over a distribution system, or built into power-consuming equipment. | |||
==General case== | |||
] | |||
The general expression for power factor is given by | |||
:<math> \mbox{power factor} = P/P_a </math> | |||
:<math> P_a = I_{rms} V_{rms} </math> | |||
where <math>P</math> is the real power measured by an ideal ], <math>I_{rms}</math> is the rms current measured by an ideal ], and <math>V_{rms}</math> is the rms voltage measured by an ideal ]. Apparent power, <math>P_a</math>, is the product of the rms current and the rms voltage. | |||
If the load is sourcing power back toward the generator, then <math>P</math> and <math> \mbox{power factor} </math> will be negative. | |||
===Periodic waveforms=== | |||
If the waveforms are periodic with the same fundamental period, then the power factor can be computed by the following | |||
:<math> \mbox{power factor} = \frac{P}{P_a} </math> | |||
:<blockquote><math>P =\frac{1}{T} \int_{t'}^{t'+T} i(t)v(t) dt</math></blockquote> | |||
:<blockquote><math>P_a = I_{rms} V_{rms}</math></blockquote> | |||
:<blockquote><blockquote><math>I_{rms} =\sqrt{\frac{1}{T} \int_{t'}^{t'+T} {i(t)}^2 dt}</math></blockquote></blockquote> | |||
:<blockquote><blockquote><math>V_{rms} =\sqrt{\frac{1}{T} \int_{t'}^{t'+T} {v(t)}^2 dt}</math></blockquote></blockquote> | |||
:<blockquote><math>P_a = \frac{1}{T}\sqrt{\int_{t'}^{t'+T}{i^2(t)dt}\int_{t'}^{t'+T}{v^2(t)dt}}</math></blockquote> | |||
: | |||
:<math>\mbox{power factor} = \frac{\int_{t'}^{t'+T} i(t)v(t) dt}{\sqrt{\int_{t'}^{t'+T}{i^2(t)dt}\int_{t'}^{t'+T}{v^2(t)dt}}}</math> | |||
: | |||
where <math>i(t)</math> is the instantaneous current, <math>v(t)</math> is the instantaneous voltage, <math>t'</math> is an arbitrary starting time, and <math>T</math> is the period of the waveforms. | |||
===Nonperiodic waveforms=== | |||
If the waveforms are not periodic and the physical meters have the same averaging time, then the equations for the periodic case can be used with the exception that <math>T</math> is the averaging time of the meters instead of the waveform period. | |||
{{Clear}} | |||
== Linear circuits == | == Linear circuits == | ||
] | ] | ||
] | |||
In a purely resistive AC circuit, voltage and current waveforms are in step (or in phase), changing polarity at the same instant in each cycle. All the power entering the load is consumed. Where ] loads are present, such as with ]s or ]s, energy storage in the loads results in a time difference between the current and voltage waveforms. During each cycle of the AC voltage, extra energy, in addition to any energy consumed in the load, is temporarily stored in the load in ] or ]s, and then returned to the power grid a fraction of a second later in the cycle. The "ebb and flow" of this nonproductive power increases the current in the line. Thus, a circuit with a low power factor will use higher currents to transfer a given quantity of real power than a circuit with a high power factor. A linear load does not change the shape of the waveform of the current, but may change the relative timing (phase) between voltage and current. | |||
] | |||
Circuits containing purely resistive heating elements (filament lamps, cooking stoves, etc.) have a power factor of 1.0. Circuits containing inductive or capacitive elements (electric motors, ] valves, ], and others ) often have a power factor below 1.0. | |||
In a ], consisting of combinations of resistors, inductors, and capacitors, current flow has a sinusoidal response to the sinusoidal line voltage.<ref name="Das_2015">{{cite book | title = Power System Harmonics and Passive Filter Design | first = J. C. | last = Das | publisher = Wiley, IEEE Press | year = 2015 | page = 2 | ISBN = 978-1-118-86162-2 | quote = To distinguish between linear and nonlinear loads, we may say that linear time-invariant loads are characterized so that an application of a sinusoidal voltage results in a sinusoidal flow of current.}}</ref> A linear load does not change the shape of the input waveform but may change the relative timing (phase) between voltage and current, due to its inductance or capacitance. | |||
===Definition and calculation=== | |||
AC power flow has the three components: real power (also known as active power) (P), measured in ]s (W); apparent power (S), measured in ]s (VA); and reactive power (Q), measured in ] (var).<ref>http://www.iec.ch/zone/si/si_elecmag.htm</ref> | |||
In a purely resistive AC circuit, voltage and current waveforms are in step (or ]), changing polarity at the same instant in each cycle. All the power entering the load is consumed (or dissipated). | |||
The power factor is defined as: | |||
Where ] loads are present, such as with ]s or ]s, energy storage in the loads results in a phase difference between the current and voltage waveforms. During each cycle of the AC voltage, extra energy, in addition to any energy consumed in the load, is temporarily stored in the load in ] or ]s then returned to the power grid a fraction of the period later. | |||
:<math>\frac{P}{S}</math>. | |||
Electrical circuits containing predominantly resistive loads (], devices using ] like ] and ]) have a power factor of almost 1, but circuits containing inductive or capacitive loads (electric motors, ] valves, transformers, ], and others) can have a power factor well below 1. | |||
In the case of a perfectly ] waveform, P, Q and S can be expressed as vectors that form a ] triangle such that: | |||
A circuit with a low power factor will use a greater amount of current to transfer a given quantity of real power than a circuit with a high power factor thus causing increased losses due to ] in power lines, and requiring the use of higher-rated conductors and transformers. | |||
:<math>S^2\,\! = {P^2\,\!} + {Q^2\,\!}.</math> | |||
=== Definition and calculation === | |||
If <math>\varphi</math> is the ] between the current and voltage, then the power factor is equal to the ] of the angle, <math>\left|\cos\varphi\right|</math>, and: | |||
] has two components: | |||
* ] (<math>P</math>) (sometimes called average power<ref>{{Cite book|title=Introductory Circuit Analysis|last=Boylestad|first=Robert|isbn=978-0-13-097417-4|edition=10th|date=2002-03-04|page=857}}</ref>), expressed in ]s (W) | |||
* ] (<math>Q</math>), usually expressed in ] (var)<ref>{{cite web |title=SI Units – Electricity and Magnetism |publisher = International Electrotechnical Commission |url=http://www.iec.ch/zone/si/si_elecmag.htm | place = ] | archive-url = https://web.archive.org/web/20071211234311/http://www.iec.ch/zone/si/si_elecmag.htm#si_epo |archive-date = 2007-12-11 |access-date= 14 June 2013}}</ref> | |||
Together, they form the ] (<math>S</math>) expressed as ] (VA). The magnitude of the complex power is the apparent power (<math>|S|</math>), also expressed in volt-amperes (VA). | |||
:<math> |P| = |S| \left|\cos\varphi\right|. </math> | |||
The VA and var are non-SI units dimensionally similar to the watt but are used in engineering practice instead of the watt to state what ] is being expressed. The ] explicitly disallows using units for this purpose or as the only source of information about a physical quantity as used.<ref>{{cite book|title=The International System of Units (SI) |url=https://www.bipm.org/documents/20126/41483022/si_brochure_8.pdf |archive-url=https://web.archive.org/web/20220319080426/https://www.bipm.org/documents/20126/41483022/si_brochure_8.pdf |archive-date=2022-03-19 |url-status=live|year=2006|publisher=]|location=§ 5.3.2 (p. 132, 40 in the ] file)}}</ref> | |||
Since the units are consistent, the power factor is by definition a ] between -1 and 1. When power factor is equal to 0, the energy flow is entirely reactive, and stored energy in the load returns to the source on each cycle. When the power factor is 1, all the energy supplied by the source is consumed by the load. Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle. Capacitive loads are leading (current leads voltage), and inductive loads are lagging (current lags voltage). | |||
The power factor is defined as the ratio of real power to apparent power. As power is transferred along a transmission line, it does not consist purely of real power that can do work once transferred to the load, but rather consists of a combination of real and reactive power, called apparent power. The power factor describes the amount of real power transmitted along a transmission line relative to the total apparent power flowing in the line.<ref>{{Citation | publisher = ] | id = Std. 100 | title = Authoritative Dictionary of Standards Terms | edition = 7th | isbn = 978-0-7381-2601-2| year = 2000 }}</ref><ref>{{Citation | publisher = IEEE | id = Std. 1459–2000 | title = Trial-Use Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions | year = 2000 | ISBN = 978-0-7381-1963-2}}. Note 1, section 3.1.1.1, when defining the quantities for power factor, asserts that real power only flows to the load and can never be negative. As of 2013, one of the authors acknowledged that this note was incorrect, and is being revised for the next edition. See http://powerstandards.com/Shymanski/draft.pdf {{Webarchive|url=https://web.archive.org/web/20160304071333/http://powerstandards.com/Shymanski/draft.pdf |date=2016-03-04 }}</ref> | |||
If a purely resistive load is connected to a power supply, current and voltage will change polarity in step, the power factor will be unity (1), and the electrical energy flows in a single direction across the network in each cycle. Inductive loads such as transformers and motors (any type of wound coil) consume reactive power with current waveform lagging the voltage. Capacitive loads such as capacitor banks or buried cable generate reactive power with current phase leading the voltage. Both types of loads will absorb energy during part of the AC cycle, which is stored in the device's magnetic or electric field, only to return this energy back to the source during the rest of the cycle. | |||
The power factor can also be computed as the cosine of the angle θ by which the current waveform lags or leads the voltage waveform.<ref name="SureshKumar_2013">{{cite book | title = Electric Circuit Analysis | first = K. S. | last = Suresh Kumar | publisher = Pearson | year = 2013 | page = 8.10 | isbn = 978-8-13-179155-4}}</ref> | |||
For example, to get 1 kW of real power, if the power factor is unity, 1 kVA of apparent power needs to be transferred (1 kW ÷ 1 = 1 kVA). At low values of power factor, more apparent power needs to be transferred to get the same real power. To get 1 kW of real power at 0.2 power factor, 5 kVA of apparent power needs to be transferred (1 kW ÷ 0.2 = 5 kVA). This apparent power must be produced and transmitted to the load in the conventional fashion, and is subject to the usual distributed losses in the production and transmission processes. | |||
==== Power triangle ==== | |||
Electrical loads consuming ] consume both real power and reactive power. The vector sum of real and reactive power is the apparent power. The presence of reactive power causes the real power to be less than the apparent power, and so, the electric load has a power factor of less than 1. | |||
] | |||
One can relate the various components of AC power by using the power triangle in vector space. Real power extends horizontally in the real axis and reactive power extends in the direction of the imaginary axis. Complex power (and its magnitude, apparent power) represents a combination of both real and reactive power, and therefore can be calculated by using the vector sum of these two components. We can conclude that the mathematical relationship between these components is: | |||
===Power factor correction of linear loads=== | |||
A high power factor is generally desirable in a transmission system to reduce transmission losses and improve voltage regulation at the load. It is often desirable to adjust the power factor of a system to near 1.0. When reactive elements supply or absorb reactive power near the load, the apparent power is reduced. Power factor correction may be applied by an ] utility to improve the stability and efficiency of the transmission network. Individual electrical customers who are charged by their utility for low power factor may install correction equipment to reduce those costs. | |||
:<math>\begin{align} | |||
Power factor correction brings the power factor of an AC power circuit closer to 1 by supplying reactive power of opposite sign, adding capacitors or inductors that act to cancel the inductive or capacitive effects of the load, respectively. For example, the inductive effect of motor loads may be offset by locally connected capacitors. If a load had a ] value, inductors (also known as ''reactors'' in this context) are connected to correct the power factor. In the electricity industry, inductors are said to ''consume'' reactive power and capacitors are said to ''supply'' it, even though the energy is just moving back and forth on each AC cycle. | |||
S &= P + jQ \\ | |||
|S| &= \sqrt{P^2 + Q^2} \\ | |||
\text{pf} &= \cos{\theta} = \frac{P}{|S|} = \cos{ \left( \arctan{ \left( \frac{Q}{P} \right) } \right) } \\ | |||
Q &= P \, \tan(\arccos(\text{pf})) | |||
\end{align}</math> | |||
As the angle θ increases with fixed total apparent power, current and voltage are further out of phase with each other. Real power decreases, and reactive power increases. | |||
The reactive elements can create voltage fluctuations and harmonic noise when switched on or off. They will supply or sink reactive power regardless of whether there is a corresponding load operating nearby, increasing the system's no-load losses. In the worst case, reactive elements can interact with the system and with each other to create resonant conditions, resulting in system instability and severe ] fluctuations. As such, reactive elements cannot simply be applied without engineering analysis. | |||
==== Lagging, leading and unity power factors ==== | |||
]; 2. Network connection points; 3. ]; 4. Inrush Limiting ]s; 5. ]s (single-phase or three-phase units, delta-connection); 6. ] for controls and ventilation fans) ]] | |||
Power factor is described as ''leading'' if the current waveform is advanced in phase concerning voltage, or ''lagging'' when the current waveform is behind the voltage waveform. A lagging power factor signifies that the load is inductive, as the load will ''consume'' reactive power. The reactive component <math>Q</math> is positive as reactive power travels through the circuit and is ''consumed'' by the inductive load. A leading power factor signifies that the load is capacitive, as the load ''supplies'' reactive power, and therefore the reactive component <math>Q</math> is negative as reactive power is being supplied to the circuit. | |||
] | |||
An '''automatic power factor correction unit''' consists of a number of ]s that are switched by means of ]s. These contactors are controlled by a regulator that measures power factor in an electrical network. Depending on the load and power factor of the network, the power factor controller will switch the necessary blocks of capacitors in steps to make sure the power factor stays above a selected value. | |||
If θ is the ] between the current and voltage, then the power factor is equal to the ] of the angle, <math>\cos\theta</math>: | |||
Instead of using a set of switched ]s, an unloaded ] can supply reactive power. The ] drawn by the synchronous motor is a function of its field excitation. This is referred to as a '']''. It is started and connected to the ]. It operates at a leading power factor and puts ]s onto the network as required to support a system’s ] or to maintain the system power factor at a specified level. | |||
:<math>|P| = |S| \cos\theta</math> | |||
Since the units are consistent, the power factor is by definition a ] between -1 and 1. When the power factor is equal to 0, the energy flow is entirely reactive, and stored energy in the load returns to the source on each cycle. When the power factor is 1, referred to as the ''unity'' power factor, all the energy supplied by the source is consumed by the load. Power factors are usually stated as ''leading'' or ''lagging'' to show the sign of the phase angle. Capacitive loads are leading (current leads voltage), and inductive loads are lagging (current lags voltage). | |||
The condenser’s installation and operation are identical to large ]s. Its principal advantage is the ease with which the amount of correction can be adjusted; it behaves like an electrically variable capacitor. Unlike capacitors, the amount of reactive power supplied is proportional to voltage, not the square of voltage; this improves voltage stability on large networks. Synchronous condensors are often used in connection with ] transmission projects or in large industrial plants such as ]s. | |||
If a purely resistive load is connected to a power supply, current and voltage will change polarity in step, the power factor will be 1, and the electrical energy flows in a single direction across the network in each cycle. Inductive loads such as induction motors (any type of wound coil) consume reactive power with the current waveform lagging the voltage. Capacitive loads such as capacitor banks or buried cables generate reactive power with the current phase leading the voltage. Both types of loads will absorb energy during part of the AC cycle, which is stored in the device's magnetic or electric field, only to return this energy back to the source during the rest of the cycle. | |||
For power factor correction of high-voltage power systems or large, fluctuating industrial loads, power electronic devices such as the ] or ] are increasingly used. These systems are able to compensate sudden changes of power factor much more rapidly than contactor-switched capacitor banks, and being solid-state require less maintenance than synchronous condensers. | |||
For example, to get 1 kW of real power, if the power factor is unity, 1 kVA of apparent power needs to be transferred (1 kW ÷ 1 = 1 kVA). At low values of power factor, more apparent power needs to be transferred to get the same real power. To get 1 kW of real power at 0.2 power factor, 5 kVA of apparent power needs to be transferred (1 kW ÷ 0.2 = 5 kVA). This apparent power must be produced and transmitted to the load and is subject to losses in the production and transmission processes. | |||
==Non-linear loads== | |||
A non-linear load on a power system is typically a rectifier (such as used in a power supply), or some kind of arc discharge device such as a ], electric ] machine, or ]. Because current in these systems is interrupted by a switching action, the current contains frequency components that are multiples of the power system frequency. Distortion power factor is a measure of how much the harmonic distortion of a load current decreases the average power transferred to the load. | |||
] | |||
Electrical loads consuming ] consume both real power and reactive power. The vector sum of real and reactive power is the complex power, and its magnitude is the apparent power. The presence of reactive power causes the real power to be less than the apparent power, and so, the electric load has a power factor of less than 1. | |||
===Non-sinusoidal components=== | |||
Non-linear loads change the shape of the current waveform from a ] to some other form. Non-linear loads create ] currents in addition to the original (fundamental frequency) AC current. Filters consisting of linear capacitors and inductors can prevent harmonic currents from entering the supplying system. | |||
A negative power factor (0 to −1) can result from returning active power to the source, such as in the case of a building fitted with solar panels when surplus power is fed back into the supply.<ref>{{Citation | title = On the resistance and electromotive forces of the electric arc |first=W. | last = Duddell | journal = Philosophical Transactions of the Royal Society A: Mathematical, Physical and Engineering Sciences|volume=203 |issue=359–371 |doi=10.1098/rsta.1904.0022 | pages = 512–15 | year = 1901 | quote = The fact that the solid arc has, at low frequencies, a negative power factor, indicates that the arc is supplying power to the alternator…| doi-access = free }}</ref><ref>{{Citation |title=Analysis of some measurement issues in bushing power factor tests in the field |first=S. |last=Zhang |journal= IEEE Transactions on Power Delivery|volume=21 |issue=3 |pages=1350–56 |date=July 2006 |quote=…(the measurement) gives both negative power factor and negative resistive current (power loss) |doi=10.1109/tpwrd.2006.874616|s2cid=39895367 }}</ref><ref>{{Citation | title = Performance of Grid-Connected Induction Generator under Naturally Commutated AC Voltage Controller |first=A. F. |last=Almarshoud |display-authors=etal |journal=Electric Power Components and Systems |volume=32 |issue=7 |pages=691–700 |year=2004 |quote=Accordingly, the generator will consume active power from the grid, which leads to negative power factor.|doi=10.1080/15325000490461064 |s2cid=110279940 }}</ref> | |||
In linear circuits having only sinusoidal currents and voltages of one frequency, the power factor arises only from the difference in phase between the current and voltage. This is "displacement power factor". The concept can be generalized to a total, distortion, or true power factor where the apparent power includes all harmonic components. This is of importance in practical power systems that contain ] loads such as ], some forms of electric lighting, ]s, welding equipment, ] and other devices. | |||
=== Power factor correction of linear loads === | |||
A typical ] will give incorrect results when attempting to measure the AC current drawn by a non-sinusoidal load; the instruments sense the average value of a rectified waveform. The average response is then calibrated to the effective, ] value. An RMS sensing multimeter must be used to measure the actual RMS currents and voltages (and therefore apparent power). To measure the real power or reactive power, a ] designed to work properly with non-sinusoidal currents must be used. | |||
] | |||
A high power factor is generally desirable in a power delivery system to reduce losses and improve voltage regulation at the load. Compensating elements near an electrical load will reduce the apparent power demand on the supply system. Power factor correction may be applied by an ] utility to improve the stability and efficiency of the network. Individual electrical customers who are charged by their utility for low power factor may install correction equipment to increase their power factor to reduce costs. | |||
Power factor correction brings the power factor of an AC power circuit closer to 1 by supplying or absorbing reactive power, adding capacitors or inductors that act to cancel the inductive or capacitive effects of the load, respectively. In the case of offsetting the inductive effect of motor loads, capacitors can be locally connected. These capacitors help to generate reactive power to meet the demand of the inductive loads. This will keep that reactive power from having to flow from the utility generator to the load. In the electricity industry, inductors are said to consume reactive power, and capacitors are said to supply it, even though reactive power is just energy moving back and forth on each AC cycle. | |||
===Distortion power factor=== | |||
The ''distortion power factor'' describes how the ] of a load current decreases the average power transferred to the load. | |||
:<math> | |||
\mbox{distortion power factor} = {1 \over \sqrt{ 1 + \mbox{THD}_i^2}} = {I_{\mbox{1, rms}} \over I_{\mbox{rms}}} | |||
</math> | |||
The reactive elements in power factor correction devices can create voltage fluctuations and harmonic noise when switched on or off. They will supply or sink reactive power regardless of whether there is a corresponding load operating nearby, increasing the system's no-load losses. In the worst case, reactive elements can interact with the system and with each other to create resonant conditions, resulting in system instability and severe ] fluctuations. As such, reactive elements cannot simply be applied without engineering analysis. | |||
<math>\mbox{THD}_i</math> is the ] of the load current. This definition assumes that the voltage stays undistorted (sinusoidal, without harmonics). This simplification is often a good approximation in practice. <math>I_{1,\mbox{rms}}</math> is the fundamental component of the current and <math>I_{\mbox{rms}}</math> is the total current - both are ]-values. | |||
]; 2. Network connection points; 3. ]; 4. Inrush-limiting ]s; 5. ]s (single-phase or three-phase units, delta-connection); 6. ] (for controls and ventilation fans) ]] | |||
The result when multiplied with the displacement power factor (DPF) is the overall, true power factor or just power factor (PF): | |||
An ''' automatic power factor correction unit''' consists of some ]s that are switched by means of ]s. These contactors are controlled by a regulator that measures power factor in an electrical network. Depending on the load and power factor of the network, the power factor controller will switch the necessary blocks of capacitors in steps to make sure the power factor stays above a selected value. | |||
In place of a set of switched ]s, an unloaded ] can supply reactive power. The ] drawn by the synchronous motor is a function of its field excitation. It is referred to as a ''']'''. It is started and connected to the ]. It operates at a leading power factor and puts ] onto the network as required to support a system's ] or to maintain the system power factor at a specified level. | |||
The synchronous condenser's installation and operation are identical to those of large ]s. Its principal advantage is the ease with which the amount of correction can be adjusted; it behaves like a variable capacitor. Unlike with capacitors, the amount of reactive power furnished is proportional to voltage, not the square of voltage; this improves voltage stability on large networks. Synchronous condensers are often used in connection with ] transmission projects or in large industrial plants such as ]s. | |||
For power factor correction of high-voltage power systems or large, fluctuating industrial loads, power electronic devices such as the ] or ] are increasingly used. These systems are able to compensate sudden changes of power factor much more rapidly than contactor-switched capacitor banks and, being solid-state, require less maintenance than synchronous condensers. | |||
== Non-linear loads == | |||
Examples of non-linear loads on a power system are rectifiers (such as used in a power supply), and arc discharge devices such as ]s, electric ] machines, or ]s. Because current in these systems is interrupted by a switching action, the current contains frequency components that are multiples of the power system frequency. ''Distortion power factor'' is a measure of how much the harmonic distortion of a load current decreases the average power transferred to the load. | |||
] | |||
=== Non-sinusoidal components === | |||
In linear circuits having only sinusoidal currents and voltages of one frequency, the power factor arises only from the difference in phase between the current and voltage. This is ''displacement power factor''.<ref name="FuchsMasoum2015">{{cite book|author1=Ewald Fuchs|author2=Mohammad A. S. Masoum|title=Power Quality in Power Systems and Electrical Machines|url=https://books.google.com/books?id=wuGcBAAAQBAJ&pg=PA432|date=14 July 2015|publisher=Elsevier Science|isbn=978-0-12-800988-8|pages=432–|quote=The DPF is the cosine of the angle between these two quantities}}</ref> | |||
Non-linear loads change the shape of the current waveform from a ] to some other form. Non-linear loads create ] currents in addition to the original (fundamental frequency) AC current. This is of importance in practical power systems that contain ] loads such as ], some forms of electric lighting, ]s, welding equipment, ], variable speed drives and other devices. Filters consisting of linear capacitors and inductors can prevent harmonic currents from entering the supplying system. | |||
To measure the real power or reactive power, a ] designed to work properly with non-sinusoidal currents must be used. | |||
=== Distortion power factor === | |||
The '''distortion power factor''' is the distortion component associated with the harmonic voltages and currents present in the system. | |||
:<math> | :<math> | ||
\begin{align} | |||
\mbox{PF} = \mbox{DPF} {I_{\mbox{1, rms}} \over I_{\mbox{rms}}} | |||
\mbox{distortion power factor} | |||
& = \frac{ I_1}{I_{rms}} \\ | |||
& = \frac{I_1} {\sqrt{I_1^2+I_2^2+I_3^2+I_4^2+\cdots}} \\ | |||
& = \frac{1} { \sqrt{1+ \frac{I_2^2+I_3^2+I_4^2+\cdots}{I_1^2}}} \\ | |||
& = \frac{1} {\sqrt{ 1+THD_i^2}} \\ | |||
\end{align} | |||
</math> | </math> | ||
<math>\mbox{THD}_i</math> is the ] of the load current. | |||
===Switched-mode power supplies=== | |||
:<math>THD_i = \frac{\sqrt{\displaystyle\sum_{h=2}^\infty I_h^2}} {I_1}= \frac{\sqrt{I_2^2+I_3^2+I_4^2+\cdots}} {I_1}</math> | |||
{{Main|switched-mode power supply#Power factor}} | |||
<math>I_1</math> is the fundamental component of the current, <math>I_{rms}</math> is the total current, and <math>I_h</math> is the current on the h<sup>th</sup> harmonic; all are ] values (distortion power factor can also be used to describe individual order harmonics, using the corresponding current in place of total current). This definition with respect to total harmonic distortion assumes that the voltage stays undistorted (sinusoidal, without harmonics). This simplification is often a good approximation for stiff voltage sources (not being affected by changes in load downstream in the distribution network). Total harmonic distortion of typical generators from current distortion in the network is on the order of 1–2%, which can have larger scale implications but can be ignored in common practice.<ref>{{Citation |url=http://ecmweb.com/power-quality/effects-harmonics-power-systems |title=Effects of Harmonics on Power Systems |first=C. |last=Sankaran |year=1999 |publisher=Electro-Test |quote=...and voltage-time relationship deviates from the pure sine function. The distortion at the point of generation is very small (about 1% to 2%), but nonetheless it exists.}}</ref> | |||
The result when multiplied with the displacement power factor is the overall, true power factor or just power factor (PF): | |||
:<math>\mbox{PF} = \frac{\cos{\varphi}} {\sqrt{ 1+THD_i^2}}</math> | |||
=== Distortion in three-phase networks === | |||
In practice, the local effects of distortion current on devices in a ] rely on the magnitude of certain order harmonics rather than the total harmonic distortion. | |||
For example, the ], or zero-sequence, harmonics (3rd, 9th, 15th, etc.) have the property of being in-phase when compared line-to-line. In a ], these harmonics can result in circulating currents in the delta windings and result in greater ]. In a wye-configuration of a transformer, triplen harmonics will not create these currents, but they will result in a non-zero current in the ]. This could overload the neutral wire in some cases | |||
and create error in kilowatt-hour metering systems and billing revenue.<ref>{{Citation | chapter-url = http://www.pge.com/includes/docs/pdfs/mybusiness/customerservice/energystatus/powerquality/harmonics.pdf | title = Power System Harmonics | publisher = Pacific Gas and Electric | chapter = Single-phase load harmonics vs. three-phase load harmonics | chapter-format = ] | access-date = 2013-11-26 | archive-date = 2015-09-24 | archive-url = https://web.archive.org/web/20150924072113/http://www.pge.com/includes/docs/pdfs/mybusiness/customerservice/energystatus/powerquality/harmonics.pdf | url-status = dead }}</ref><ref>{{Citation | chapter-url = http://energylogix.ca/harmonics_and_ieee.pdf | title = Harmonics and IEEE 519 | publisher = EnergyLogix Solutions | chapter = Harmonic Effects | place = ] | chapter-format = ]}}</ref> The presence of current harmonics in a transformer also result in larger ] in the magnetic core of the transformer. Eddy current losses generally increase as the square of the frequency, lowering the transformer's efficiency, dissipating additional heat, and reducing its service life.<ref>{{Citation |url=http://ecmweb.com/power-quality/effects-harmonics-power-systems |title=Effects of Harmonics on Power Systems |first=C. |last=Sankaran |year=1999 |publisher = Electro-Test |section=Transformers}}</ref> | |||
Negative-sequence harmonics (5th, 11th, 17th, etc.) combine 120 degrees out of phase, similarly to the fundamental harmonic but in a reversed sequence. In generators and motors, these currents produce magnetic fields which oppose the rotation of the shaft and sometimes result in damaging mechanical vibrations.<ref>{{Citation |url=http://ecmweb.com/power-quality/effects-harmonics-power-systems |title=Effects of Harmonics on Power Systems |first=C. |last=Sankaran |year=1999 |publisher=Electro-Test |section=Motors |quote=The interaction between the positive and negative sequence magnetic fields and currents produces torsional oscillations of the motor shaft. These oscillations result in shaft vibrations.}}</ref> | |||
A particularly important class of non-linear loads is the millions of personal computers that typically incorporate ] (SMPS) with rated output power ranging from a few watts to more than 1 kW. Historically, these very-low-cost power supplies incorporated a simple full-wave rectifier that conducted only when the mains instantaneous voltage exceeded the voltage on the input capacitors. This leads to very high ] input current, which also lead to a low ] and potentially serious phase and neutral loading concerns. | |||
=== Power factor correction (PFC) in non-linear loads === | |||
A typical ] first makes a DC bus, using a ] or similar circuit. The output voltage is then derived from this DC bus. The problem with this is that the ] is a non-linear device, so the input current is highly non-linear. That means that the input current has energy at ]s of the frequency of the voltage. | |||
==== Passive PFC ==== | |||
This presents a particular problem for the power companies, because they cannot compensate for the harmonic current by adding simple capacitors or inductors, as they could for the reactive power drawn by a linear load. Many jurisdictions are beginning to legally require power factor correction for all power supplies above a certain power level. | |||
The simplest way to control the ] current is to use a ] that passes current only at ] (50 or 60 Hz). The filter consists of capacitors or inductors and makes a non-linear device look more like a ] load. An example of passive PFC is a ]. | |||
A disadvantage of passive PFC is that it requires larger inductors or capacitors than an equivalent power active PFC circuit.<ref>{{Citation |url=http://www.nuvation.com/corporate/news/newsletter/fall2006/powersupply.html |publisher=Nuvation |date=Fall 2006 |title=Power Supply Design Principles: Techniques and Solutions, Part 3 |newspaper=Newsletter |first=Ben |last=Schramm |url-status=dead |archive-url=https://web.archive.org/web/20070309134617/http://www.nuvation.com/corporate/news/newsletter/fall2006/powersupply.html |archive-date=2007-03-09 }}</ref><ref>{{Citation | newspaper = Xplore | title = Quasi-active power factor correction with a variable inductive filter: theory, design and practice | volume = 18 | issue = 1 | pages = 248–255 | publisher = IEEE| doi = 10.1109/TPEL.2002.807135 | bibcode = 2003ITPE...18..248W | year = 2003 | last1 = Wolfle | first1 = W.H. | last2 = Hurley | first2 = W.G. }}</ref><ref>{{Citation |publisher=Nuigalway |type=project |url=http://www.nuigalway.ie/power_electronics/projects/quasi_active.html |place=] |title=Power electronics |contribution=Quasi-active Power Factor Correction: The Role of Variable Inductance |last1=Wölfle |first1=W. H. |last2=Hurley |first2=W. G. |access-date=2008-11-05 |archive-date=2020-08-06 |archive-url=https://web.archive.org/web/20200806105647/http://www.nuigalway.ie/power_electronics/projects/quasi_active.html |url-status=dead }}</ref> Also, in practice, passive PFC is often less effective at improving the power factor.<ref name="effi">{{Citation | url = http://www.xbitlabs.com/articles/coolers/display/atx-psu5_3.html | title = ATX Power Supply Units Roundup | publisher = xBit labs | quote = The power factor is the measure of reactive power. It is the ratio of active power to the total of active and reactive power. It is about 0.65 with an ordinary PSU, but PSUs with active PFC have a power factor of 0.97–0.99. hardware reviewers sometimes make no difference between the power factor and the efficiency factor. Although both these terms describe the effectiveness of a power supply, it is a gross mistake to confuse them. There is a very small effect from passive PFC – the power factor grows only from 0.65 to 0.7–0.75. | url-status = dead | archive-url = https://web.archive.org/web/20081120040707/http://www.xbitlabs.com/articles/coolers/display/atx-psu5_3.html | archive-date = 2008-11-20 }}</ref><ref>{{Citation|date=Mar 16, 2006 |publisher=Find articles |url=http://findarticles.com/p/articles/mi_m0EIN/is_2006_March_16/ai_n26797888 |archive-url=https://web.archive.org/web/20090901140721/http://findarticles.com/p/articles/mi_m0EIN/is_2006_March_16/ai_n26797888/ |url-status=dead |archive-date=September 1, 2009 |title=The Active PFC Market is Expected to Grow at an Annually Rate of 12.3% Till 2011 |quote=Higher-powered products are also likely to use active PFC, since it would be the most cost effective way to bring products into compliance with the EN standard. }}</ref><ref>{{Citation | url = http://www.techarp.com/showarticle.aspx?artno=81&pgno=1 | publisher = TECHarp | title = Power Factor Correction | quote = Passive PFC the power factor is low at 60–80%. Active PFC ... a power factor of up to 95%}}</ref><ref>{{Citation | publisher = Silverstone Technology | url = http://www.silverstonetek.com/tech/wh_pfc.php?area= | title = Why we need PFC in PSU | quote = Normally, the power factor value of electronic device without power factor correction is approximately 0.5. Passive PFC 70~80% Active PFC 90~99.9% | url-status = dead | archive-url = https://web.archive.org/web/20081222085515/http://www.silverstonetek.com/tech/wh_pfc.php?area= | archive-date = 2008-12-22 }}</ref><ref>{{Citation | publisher = Electronic products | newspaper = Taiyo | url = http://www2.electronicproducts.com/PFC_options_for_power_supplies-article-taiyo-mar2004-html.aspx | title = PFC options for power supplies | first = Tom | last = Brooks | date = Mar 2004 | quote = The disadvantages of passive PFC techniques are that they typically yield a power factor of only 0.60 to 0.70 Dual-stage active PFC technology a power factor typically greater than 0.98 | url-status = dead | archive-url = https://web.archive.org/web/20081202100831/http://www2.electronicproducts.com/PFC_options_for_power_supplies-article-taiyo-mar2004-html.aspx | archive-date = 2008-12-02 }}</ref> | |||
Regulatory agencies such as the ] have set harmonic limits as a method of improving power factor. Declining component cost has hastened implementation of two different methods. To comply with current EU standard EN61000-3-2, all ] with output power more than 75 W must include passive power factor correction, at least. ] power supply certification requires a power factor of 0.9 or more.<ref>http://www.80plus.org, 80 PLUS Certified Power Supplies and Manufacturers; see section ''What is an 80 PLUS certified power supply?''</ref> | |||
==== Active PFC ==== | |||
===Power factor correction in non-linear loads=== | |||
] showing active PFC rating]] | |||
Active PFC is the use of ] to change the waveform of current drawn by a load to improve the power factor.<ref>{{Citation | publisher = Fairchild Semiconductor | year = 2004 | type = application note | number = 42047 | title = Power Factor Correction (PFC) Basics | url = http://www.fairchildsemi.com/an/AN/AN-42047.pdf | access-date = 2009-11-29 | archive-url = https://web.archive.org/web/20140611063712/http://www.fairchildsemi.com/an/AN/AN-42047.pdf | archive-date = 2014-06-11 | url-status = dead }}</ref> Some types of the active PFC are ], ], ] and ]. Active power factor correction can be single-stage or multi-stage. | |||
====Passive PFC==== | |||
The simplest way to control the ] current is to use a ]: it is possible to design a filter that passes current only at ]. This filter reduces the harmonic current, which means that the non-linear device now looks like a ] load. At this point the power factor can be brought to near unity, using capacitors or inductors as required. This filter requires large-value high-current inductors, however, which are bulky and expensive. | |||
In the case of a switched-mode power supply, a ] is inserted between the bridge rectifier and the main input capacitors. The boost converter attempts to maintain a constant voltage at its output while drawing a current that is always in phase with and at the same frequency as the line voltage. Another switched-mode converter inside the power supply produces the desired output voltage from the DC bus. This approach requires additional semiconductor switches and control electronics but permits cheaper and smaller passive components. It is frequently used in practice. | |||
A passive PFC requires an inductor larger than the inductor in an active PFC, but costs less.<ref> | |||
by Ben Schramm</ref><ref> and | |||
by Wolfle, W.H.; Hurley, W.G.</ref> | |||
For a three-phase SMPS, the ] configuration may be used to substantially improve the power factor. | |||
This is a simple way of correcting the nonlinearity of a load by using capacitor banks. It is not as effective as active PFC.<ref name="effi"> | |||
] with passive PFC can achieve power factor of about 0.7–0.75, SMPSs with active PFC, up to 0.99 power factor, while a SMPS without any power factor correction have a power factor of only about 0.55–0.65.<ref>{{Citation |last1=Sugawara |first1=I. |last2=Suzuki |first2=Y. |last3=Takeuchi |first3=A. |last4=Teshima |first4=T. |contribution=Experimental studies on active and passive PFC circuits |title=INTELEC 97, 19th International Telecommunications Energy Conference |date=19–23 Oct 1997 |pages=571–78 |doi=10.1109/INTLEC.1997.646051|isbn=978-0-7803-3996-5 |s2cid=109885369 }}</ref> | |||
The power factor is the measure of reactive power. It is the ratio of active power to the total of active and reactive power. It is about 0.65 with an ordinary PSU, but PSUs with active PFC have a power factor of 0.97-0.99. ... hardware reviewers sometimes make no difference between the power factor and the efficiency factor. Although both these terms describe the effectiveness of a power supply, it is a gross mistake to confuse them. ... There is a very small effect from passive PFC – the power factor grows only from 0.65 to 0.7-0.75." | |||
</ref><ref> | |||
"Higher-powered products are also likely to use active PFC, since it would be the most cost effective way to bring products into compliance with the EN standard." | |||
</ref><ref> | |||
"Passive PFC ... the power factor is low at 60-80%. ... Active PFC ... a power factor of up to 95%" | |||
</ref><ref> | |||
"Normally, the power factor value of electronic device without power factor correction is approximately 0.5. ... Passive PFC ... 70~80% ... Active PFC ... 90~99.9%" | |||
</ref><ref> | |||
by Tom Brooks 2004 | |||
"The disadvantages of passive PFC techniques are that they typically yield a power factor of only 0.60 to 0.70 ... Dual-stage active PFC technology a power factor typically greater than 0.98" | |||
</ref> | |||
One example of this is a ]. | |||
Due to their very wide input voltage range, many power supplies with active PFC can automatically adjust to operate on AC power from about 100 V (Japan) to 240 V (Europe). That feature is particularly welcome in power supplies for laptops. | |||
Passive PFCs are typically more power efficient than active PFCs. ''Efficiency'' is not to be confused with the PFC, though many computer hardware reviews conflate them.<ref name="effi"/> A passive PFC on a switching computer PSU has a typical power efficiency of around 96%, while an active PFC has a typical efficiency of about 94%.<ref> | |||
</ref> | |||
==== |
==== Dynamic PFC ==== | ||
Dynamic power factor correction (DPFC), sometimes referred to as real-time power factor correction, is used for electrical stabilization in cases of rapid load changes (e.g. at large manufacturing sites). DPFC is useful when standard power factor correction would cause over or under correction.<ref>{{Cite conference|last1=Chavez |first1=C. |last2=Houdek |first2=J. A. |title=Dynamic Harmonic Mitigation and power factor correction |publisher=IEEE |book-title= EPQU'07 |conference=9th International Conference Electrical Power Quality and Utilisation: October 9–11, 2007, Barcelona, Spain |pages=1–5 |doi=10.1109/EPQU.2007.4424144 |isbn=978-84-690-9441-9 }}</ref> DPFC uses semiconductor switches, typically ]s, to quickly connect and disconnect capacitors or inductors to improve power factor. | |||
An "active power factor corrector" (active PFC) is a ] system that changes the waveshape of current drawn by a load to improve the power factor. The purpose is to make the load circuitry that is power factor corrected appear purely resistive (] equal to ]).<ref>Fairchild Semiconductor (2004). ''Application Note 42047 Power Factor Correction (PFC) Basics.'' Retrieved from http://www.fairchildsemi.com/an/AN/AN-42047.pdf</ref> In this case, the voltage and current are in phase and the ] consumption is zero. This enables the most efficient delivery of electrical power from the power company to the consumer.<ref>Bollen, M. H. J. (1999). ''Understanding Power Quality Problems: Voltage Sags and Interruptions''. Piscataway, NJ: Wiley-IEEE Press</ref> | |||
== Importance in distribution systems == | |||
] showing Active PFC rating]] | |||
] | |||
] | |||
Power factors below 1.0 require a utility to generate more than the minimum volt-amperes necessary to supply the real power (watts). This increases generation and transmission costs. For example, if the load power factor were as low as 0.7, the apparent power would be 1.4 times the real power used by the load. Line current in the circuit would also be 1.4 times the current required at 1.0 power factor, so the losses in the circuit would be doubled (since they are proportional to the square of the current). Alternatively, all components of the system such as generators, conductors, transformers, and switchgear would be increased in size (and cost) to carry the extra current. When the power factor is close to unity, for the same kVA rating of the transformer more load current can be supplied.<ref>{{cite web|url=https://www.electricalclassroom.com/power-factor/|title=Power Factor – Importance, Calculation and Correction techniques|date=23 November 2018}}</ref> | |||
Utilities typically charge additional costs to commercial customers who have a power factor below some limit, which is typically 0.9 to 0.95. Engineers are often interested in the power factor of a load as one of the factors that affect the efficiency of power transmission. | |||
Some types of active PFC are: | |||
* ] | |||
* ] | |||
* ] | |||
Active power factor correctors can be single-stage or multi-stage. | |||
With the rising cost of energy and concerns over the efficient delivery of power, active PFC has become more common in consumer electronics.<ref>{{Citation | publisher = ON Semiconductor | year = 2007 | title = Power Factor Correction Handbook | url = http://www.onsemi.com/pub_link/Collateral/HBD853-D.PDF }}</ref> Current ] guidelines for computers<ref>{{Citation | place = US | url = http://www.energystar.gov/ia/partners/prod_development/revisions/downloads/computer/Version5.0_Computer_Spec.pdf | publisher = Energy Star | title = Program Requirements for Computers | edition = Version 5.0}}</ref> call for a power factor of ≥ 0.9 at 100% of rated output in the ]. According to a white paper authored by Intel and the ], PCs with internal power supplies will require the use of active power factor correction to meet the ENERGY STAR 5.0 Program Requirements for Computers.<ref>{{Citation |last1=Bolioli |first1=T. |last2=Duggirala |first2=M. |last3=Haines |first3=E. |last4=Kolappan |first4=R. |last5=Wong |first5=H. |year=2009 |publisher=Energy Star |title=Version 5.0 System Implementation |type=white paper |url=http://www.energystar.gov/ia/partners/product_specs/program_reqs/Computers_Intel_Whitepaper_Spec5.pdf |archive-url=https://ghostarchive.org/archive/20221009/http://www.energystar.gov/ia/partners/product_specs/program_reqs/Computers_Intel_Whitepaper_Spec5.pdf |archive-date=2022-10-09 |url-status=live}}</ref> | |||
In the case of a switched-mode power supply, a ] is inserted between the bridge rectifier and the main input capacitors. The boost converter attempts to maintain a constant DC bus voltage on its output while drawing a current that is always in phase with and at the same frequency as the line voltage. Another switchmode converter inside the power supply produces the desired output voltage from the DC bus. This approach requires additional semiconductor switches and control electronics, but permits cheaper and smaller passive components. It is frequently used in practice. For example, ] with passive PFC can achieve power factor of about 0.7–0.75, SMPS with active PFC, up to 0.99 power factor, while a SMPS without any power factor correction has a power factor of only about 0.55–0.65.<ref>Sugawara, I., Suzuki, Y., Takeuchi, A., & Teshima, T. (1997). ''Experimental studies on active and passive PFC circuits''. Telecommunications Energy Conference, 1997. INTELEC 97., 19th International 19-23 Oct 1997. 571-578. doi 10.1109/INTLEC.1997.646051.</ref> | |||
In Europe, ] requires power factor correction be incorporated into consumer products. | |||
Due to their very wide input voltage range, many power supplies with active PFC can automatically adjust to operate on AC power from about 100 V (Japan) to 230 V (Europe). That feature is particularly welcome in power supplies for laptops. | |||
Small customers, such as households, are not usually charged for reactive power and so power factor metering equipment for such customers will not be installed. | |||
==Importance of power factor in distribution systems== | |||
] | |||
Power factors below 1.0 require a utility to generate more than the minimum volt-amperes necessary to supply the real power (watts). This increases generation and transmission costs. For example, if the load power factor were as low as 0.7, the apparent power would be 1.4 times the real power used by the load. Line current in the circuit would also be 1.4 times the current required at 1.0 power factor, so the losses in the circuit would be doubled (since they are proportional to the square of the current). Alternatively all components of the system such as generators, conductors, transformers, and switchgear would be increased in size (and cost) to carry the extra current. | |||
== Measurement techniques == | |||
Utilities typically charge additional costs to customers who have a power factor below some limit, which is typically 0.9 to 0.95. Engineers are often interested in the power factor of a load as one of the factors that affect the efficiency of power transmission. | |||
The power factor in a single-phase circuit (or balanced three-phase circuit) can be measured with the wattmeter-ammeter-voltmeter method, where the power in watts is divided by the product of measured voltage and current. The power factor of a balanced ] is the same as that of any phase. The power factor of an unbalanced polyphase circuit is not uniquely defined. | |||
A direct reading power factor meter can be made with a ] of the electrodynamic type, carrying two perpendicular coils on the moving part of the instrument. The field of the instrument is energized by the circuit current flow. The two moving coils, A and B, are connected in parallel with the circuit load. One coil, A, will be connected through a resistor and the second coil, B, through an inductor, so that the current in coil B is delayed with respect to current in A. At unity power factor, the current in A is in phase with the circuit current, and coil A provides maximum torque, driving the instrument pointer toward the 1.0 mark on the scale. At zero power factor, the current in coil B is in phase with circuit current, and coil B provides torque to drive the pointer towards 0. At intermediate values of power factor, the torques provided by the two coils add and the pointer takes up intermediate positions.<ref>{{Citation |first1=Donald G. |last1=Fink |author1-link=Donald G. Fink |first2=H. Wayne |last2=Beaty |title=Standard Handbook for Electrical Engineers |edition=11 |publisher=McGraw-Hill |place=New York |year=1978 |isbn=978-0-07-020974-9 |page=3‐29 paragraph 80}}</ref> | |||
With the rising cost of energy and concerns over the efficient delivery of power, active PFC has become more common in consumer electronics.<ref>ON Semiconductor (2007). ''Power Factor Correction Handbook''. Retrieved from http://www.onsemi.com/pub_link/Collateral/HBD853-D.PDF</ref> Current ] guidelines for computers () call for a power factor of ≥ 0.9 at 100% of rated output in the ]. According to a white paper authored by Intel and the ], PCs with internal power supplies will require the use of active power factor correction to meet the ENERGY STAR 5.0 Program Requirements for Computers.<ref>Bolioli, T., Duggirala, M., Haines, E., Kolappan, R., & Wong, H. (2009). ''ENERGY STAR* Version 5.0 System Implementation'' . Retrieved from http://www.energystar.gov/ia/partners/product_specs/program_reqs/Computers_Intel_Whitepaper_Spec5.pdf</ref> | |||
Another electromechanical instrument is the polarized-vane type.<ref>{{Citation |title=Manual of Electric Instruments Construction and Operating Principles |id=GET-1087A |publisher=General Electric, Meter and Instrument Department |place=Schenectady, New York |year=1949 |pages=66–68}}</ref> In this instrument a stationary field coil produces a rotating magnetic field, just like a polyphase motor. The field coils are connected either directly to polyphase voltage sources or to a phase-shifting reactor if a single-phase application. A second stationary field coil, perpendicular to the voltage coils, carries a current proportional to current in one phase of the circuit. The moving system of the instrument consists of two vanes that are magnetized by the current coil. In operation, the moving vanes take up a physical angle equivalent to the electrical angle between the voltage source and the current source. This type of instrument can be made to register for currents in both directions, giving a four-quadrant display of power factor or phase angle. | |||
In Europe, IEC 555-2 requires power factor correction be incorporated into consumer products.<ref>{{cite web |url=http://www.ce-mag.com/99ARG/Martin103.html |title=Harmonic Currents |author=Robert F. Martin |publisher=Compliance Engineering |accessdate=2010-06-16}}</ref> | |||
Digital instruments exist that directly measure the time lag between voltage and current waveforms. Low-cost instruments of this type measure the peak of the waveforms. More sophisticated versions measure the peak of the fundamental harmonic only, thus giving a more accurate reading for phase angle on distorted waveforms. Calculating power factor from voltage and current phases is only accurate if both waveforms are sinusoidal.<ref name=ni_white_paper>{{cite web|url=http://www.ni.com/white-paper/4278/en/|title=The Fundamentals of FFT-Based Signal Analysis and Measurement in LabVIEW and LabWindows/CVI|work=National Instruments Corporation|access-date=6 November 2017}}</ref> | |||
==Measuring the power factor== | |||
The power factor in a single-phase circuit (or balanced three-phase circuit) can be measured with the wattmeter-ammeter-voltmeter method, where the power in watts is divided by the product of measured voltage and current. The power factor of a balanced polyphase circuit is the same as that of any phase. The power factor of an unbalanced polyphase circuit is not uniquely defined. | |||
Power Quality Analyzers, often referred to as Power Analyzers, make a digital recording of the voltage and current waveform (typically either one phase or three phase) and accurately calculate true power (watts), apparent power (VA) power factor, AC voltage, AC current, DC voltage, DC current, frequency, IEC61000-3-2/3-12 Harmonic measurement, IEC61000-3-3/3-11 flicker measurement, individual phase voltages in delta applications where there is no neutral line, total harmonic distortion, phase and amplitude of individual voltage or current harmonics, etc.<ref name=Yokogawa_WT3000E>{{cite web|url=http://www.yokogawa.co.jp/ftp/dist/ks/catalog/en/BUWT3000E-01EN_020.pdf|title=WT3000E Series Precision Power Analyzers|work=Yokogawa Corporation|access-date=6 November 2017|archive-url=https://web.archive.org/web/20171107112155/http://www.yokogawa.co.jp/ftp/dist/ks/catalog/en/BUWT3000E-01EN_020.pdf|archive-date=7 November 2017|url-status=dead}}</ref><ref name=Fluke_1760>{{cite web|url=https://cdn.testequity.com/documents/pdf/1760-ds.pdf |archive-url=https://ghostarchive.org/archive/20221009/https://cdn.testequity.com/documents/pdf/1760-ds.pdf |archive-date=2022-10-09 |url-status=live|title=Fluke 1760 Three-Phase Power Quality Recorder |work=Fluke Corporation|access-date=6 November 2017}}</ref> | |||
A direct reading power factor meter can be made with a ] of the electrodynamic type, carrying two perpendicular coils on the moving part of the instrument. The field of the instrument is energized by the circuit current flow. The two moving coils, A and B, are connected in parallel with the circuit load. One coil, A, will be connected through a resistor and the second coil, B, through an inductor, so that the current in coil B is delayed with respect to current in A. At unity power factor, the current in A is in phase with the circuit current, and coil A provides maximum torque, driving the instrument pointer toward the 1.0 mark on the scale. At zero power factor, the current in coil B is in phase with circuit current, and coil B provides torque to drive the pointer towards 0. At intermediate values of power factor, the torques provided by the two coils add and the pointer takes up intermediate positions.<ref>] and H. Wayne Beaty, Standard Handbook for Electrical Engineers, Eleventh Edition,McGraw-Hill, New York, 1978, ISBN 0-07-020974-X page 3-29 paragraph 80</ref> | |||
== Mnemonics == | |||
Another electromechanical instrument is the polarized-vane type.<ref>Meter and Instrument Department, ''Manual of Electric Instruments Construction and Operating Principles, Manual GET-1087A'', General Electric Company, Schenectady, New York, 1949 pp. 66–68</ref> In this instrument a stationary field coil produces a rotating magnetic field, just like a polyphase motor. The field coils are connected either directly to polyphase voltage sources or to a phase-shifting reactor if a single-phase application. A second stationary field coil, perpendicular to the voltage coils, carries a current proportional to current in one phase of the circuit. The moving system of the instrument consists of two vanes that are magnetized by the current coil. In operation the moving vanes take up a physical angle equivalent to the electrical angle between the voltage source and the current source. This type of instrument can be made to register for currents in both directions, giving a four-quadrant display of power factor or phase angle. | |||
Anglophone power engineering students are advised to remember: | |||
''ELI the ICE man'' or ''ELI on ICE'' – the voltage E, leads the current I, in an inductor L. The current I leads the voltage E in a capacitor C. | |||
Another common mnemonic is CIVIL – in a capacitor (C) the current (I) leads voltage (V), voltage (V) leads current (I) in an inductor (L). | |||
Digital instruments can be made that either directly measure the time lag between voltage and current waveforms and so calculate the power factor, or by measuring both true and apparent power in the circuit and calculating the quotient. The first method is only accurate if voltage and current are sinusoidal; loads such as rectifiers distort the waveforms from the sinusoidal shape. | |||
== |
== References == | ||
{{Reflist}} | |||
English-language power engineering students are advised to remember: | |||
"ELI the ICE man" or "ELI on ICE" – the voltage E leads the current I in an inductor L; the current leads the voltage in a capacitor C. | |||
Another common mnemonic is CIVIL – in a capacitor (C) the current (I) leads voltage (V), voltage (V) leads current (I) in an inductor (L). | |||
== External links == | |||
==References== | |||
* {{Citation | url = http://www.ece.utexas.edu/~grady/POWERFAC.pdf | title = Harmonics and how they relate to power factor | publisher = U Texas | access-date = 2010-09-20 | archive-date = 2011-09-27 | archive-url = https://web.archive.org/web/20110927074032/http://www.ece.utexas.edu/~grady/POWERFAC.pdf | url-status = dead }}. | |||
{{Reflist|30em}} | |||
{{Electricity delivery}} | |||
==External links== | |||
{{Authority control}} | |||
* | |||
*, NIST, December 15, 2009 | |||
{{DEFAULTSORT:Power Factor}} | |||
<!--Categories--> | |||
] | ] | ||
] | ] | ||
] | ] | ||
] |
Latest revision as of 09:54, 15 December 2024
Ratio of active power to apparent power For the firearms cartridge ranking system, see Power factor (shooting sports).In electrical engineering, the power factor of an AC power system is defined as the ratio of the real power absorbed by the load to the apparent power flowing in the circuit. Real power is the average of the instantaneous product of voltage and current and represents the capacity of the electricity for performing work. Apparent power is the product of root mean square (RMS) current and voltage. Due to energy stored in the load and returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn from the source, the apparent power may be greater than the real power, so more current flows in the circuit than would be required to transfer real power alone. A power factor magnitude of less than one indicates the voltage and current are not in phase, reducing the average product of the two. A negative power factor occurs when the device (normally the load) generates real power, which then flows back towards the source.
In an electric power system, a load with a low power factor draws more current than a load with a high power factor for the same amount of useful power transferred. The larger currents increase the energy lost in the distribution system and require larger wires and other equipment. Because of the costs of larger equipment and wasted energy, electrical utilities will usually charge a higher cost to industrial or commercial customers with a low power factor.
Power-factor correction increases the power factor of a load, improving efficiency for the distribution system to which it is attached. Linear loads with a low power factor (such as induction motors) can be corrected with a passive network of capacitors or inductors. Non-linear loads, such as rectifiers, distort the current drawn from the system. In such cases, active or passive power factor correction may be used to counteract the distortion and raise the power factor. The devices for correction of the power factor may be at a central substation, spread out over a distribution system, or built into power-consuming equipment.
General case
The general expression for power factor is given by
where is the real power measured by an ideal wattmeter, is the rms current measured by an ideal ammeter, and is the rms voltage measured by an ideal voltmeter. Apparent power, , is the product of the rms current and the rms voltage.
If the load is sourcing power back toward the generator, then and will be negative.
Periodic waveforms
If the waveforms are periodic with the same fundamental period, then the power factor can be computed by the following
where is the instantaneous current, is the instantaneous voltage, is an arbitrary starting time, and is the period of the waveforms.
Nonperiodic waveforms
If the waveforms are not periodic and the physical meters have the same averaging time, then the equations for the periodic case can be used with the exception that is the averaging time of the meters instead of the waveform period.
Linear circuits
In a linear circuit, consisting of combinations of resistors, inductors, and capacitors, current flow has a sinusoidal response to the sinusoidal line voltage. A linear load does not change the shape of the input waveform but may change the relative timing (phase) between voltage and current, due to its inductance or capacitance.
In a purely resistive AC circuit, voltage and current waveforms are in step (or in phase), changing polarity at the same instant in each cycle. All the power entering the load is consumed (or dissipated).
Where reactive loads are present, such as with capacitors or inductors, energy storage in the loads results in a phase difference between the current and voltage waveforms. During each cycle of the AC voltage, extra energy, in addition to any energy consumed in the load, is temporarily stored in the load in electric or magnetic fields then returned to the power grid a fraction of the period later.
Electrical circuits containing predominantly resistive loads (incandescent lamps, devices using heating elements like electric toasters and ovens) have a power factor of almost 1, but circuits containing inductive or capacitive loads (electric motors, solenoid valves, transformers, fluorescent lamp ballasts, and others) can have a power factor well below 1.
A circuit with a low power factor will use a greater amount of current to transfer a given quantity of real power than a circuit with a high power factor thus causing increased losses due to resistive heating in power lines, and requiring the use of higher-rated conductors and transformers.
Definition and calculation
AC power has two components:
- Real power or active power () (sometimes called average power), expressed in watts (W)
- Reactive power (), usually expressed in reactive volt-amperes (var)
Together, they form the complex power () expressed as volt-amperes (VA). The magnitude of the complex power is the apparent power (), also expressed in volt-amperes (VA).
The VA and var are non-SI units dimensionally similar to the watt but are used in engineering practice instead of the watt to state what quantity is being expressed. The SI explicitly disallows using units for this purpose or as the only source of information about a physical quantity as used.
The power factor is defined as the ratio of real power to apparent power. As power is transferred along a transmission line, it does not consist purely of real power that can do work once transferred to the load, but rather consists of a combination of real and reactive power, called apparent power. The power factor describes the amount of real power transmitted along a transmission line relative to the total apparent power flowing in the line.
The power factor can also be computed as the cosine of the angle θ by which the current waveform lags or leads the voltage waveform.
Power triangle
One can relate the various components of AC power by using the power triangle in vector space. Real power extends horizontally in the real axis and reactive power extends in the direction of the imaginary axis. Complex power (and its magnitude, apparent power) represents a combination of both real and reactive power, and therefore can be calculated by using the vector sum of these two components. We can conclude that the mathematical relationship between these components is:
As the angle θ increases with fixed total apparent power, current and voltage are further out of phase with each other. Real power decreases, and reactive power increases.
Lagging, leading and unity power factors
Power factor is described as leading if the current waveform is advanced in phase concerning voltage, or lagging when the current waveform is behind the voltage waveform. A lagging power factor signifies that the load is inductive, as the load will consume reactive power. The reactive component is positive as reactive power travels through the circuit and is consumed by the inductive load. A leading power factor signifies that the load is capacitive, as the load supplies reactive power, and therefore the reactive component is negative as reactive power is being supplied to the circuit.
If θ is the phase angle between the current and voltage, then the power factor is equal to the cosine of the angle, :
Since the units are consistent, the power factor is by definition a dimensionless number between -1 and 1. When the power factor is equal to 0, the energy flow is entirely reactive, and stored energy in the load returns to the source on each cycle. When the power factor is 1, referred to as the unity power factor, all the energy supplied by the source is consumed by the load. Power factors are usually stated as leading or lagging to show the sign of the phase angle. Capacitive loads are leading (current leads voltage), and inductive loads are lagging (current lags voltage).
If a purely resistive load is connected to a power supply, current and voltage will change polarity in step, the power factor will be 1, and the electrical energy flows in a single direction across the network in each cycle. Inductive loads such as induction motors (any type of wound coil) consume reactive power with the current waveform lagging the voltage. Capacitive loads such as capacitor banks or buried cables generate reactive power with the current phase leading the voltage. Both types of loads will absorb energy during part of the AC cycle, which is stored in the device's magnetic or electric field, only to return this energy back to the source during the rest of the cycle.
For example, to get 1 kW of real power, if the power factor is unity, 1 kVA of apparent power needs to be transferred (1 kW ÷ 1 = 1 kVA). At low values of power factor, more apparent power needs to be transferred to get the same real power. To get 1 kW of real power at 0.2 power factor, 5 kVA of apparent power needs to be transferred (1 kW ÷ 0.2 = 5 kVA). This apparent power must be produced and transmitted to the load and is subject to losses in the production and transmission processes.
Electrical loads consuming alternating current power consume both real power and reactive power. The vector sum of real and reactive power is the complex power, and its magnitude is the apparent power. The presence of reactive power causes the real power to be less than the apparent power, and so, the electric load has a power factor of less than 1.
A negative power factor (0 to −1) can result from returning active power to the source, such as in the case of a building fitted with solar panels when surplus power is fed back into the supply.
Power factor correction of linear loads
A high power factor is generally desirable in a power delivery system to reduce losses and improve voltage regulation at the load. Compensating elements near an electrical load will reduce the apparent power demand on the supply system. Power factor correction may be applied by an electric power transmission utility to improve the stability and efficiency of the network. Individual electrical customers who are charged by their utility for low power factor may install correction equipment to increase their power factor to reduce costs.
Power factor correction brings the power factor of an AC power circuit closer to 1 by supplying or absorbing reactive power, adding capacitors or inductors that act to cancel the inductive or capacitive effects of the load, respectively. In the case of offsetting the inductive effect of motor loads, capacitors can be locally connected. These capacitors help to generate reactive power to meet the demand of the inductive loads. This will keep that reactive power from having to flow from the utility generator to the load. In the electricity industry, inductors are said to consume reactive power, and capacitors are said to supply it, even though reactive power is just energy moving back and forth on each AC cycle.
The reactive elements in power factor correction devices can create voltage fluctuations and harmonic noise when switched on or off. They will supply or sink reactive power regardless of whether there is a corresponding load operating nearby, increasing the system's no-load losses. In the worst case, reactive elements can interact with the system and with each other to create resonant conditions, resulting in system instability and severe overvoltage fluctuations. As such, reactive elements cannot simply be applied without engineering analysis.
An automatic power factor correction unit consists of some capacitors that are switched by means of contactors. These contactors are controlled by a regulator that measures power factor in an electrical network. Depending on the load and power factor of the network, the power factor controller will switch the necessary blocks of capacitors in steps to make sure the power factor stays above a selected value.
In place of a set of switched capacitors, an unloaded synchronous motor can supply reactive power. The reactive power drawn by the synchronous motor is a function of its field excitation. It is referred to as a synchronous condenser. It is started and connected to the electrical network. It operates at a leading power factor and puts vars onto the network as required to support a system's voltage or to maintain the system power factor at a specified level.
The synchronous condenser's installation and operation are identical to those of large electric motors. Its principal advantage is the ease with which the amount of correction can be adjusted; it behaves like a variable capacitor. Unlike with capacitors, the amount of reactive power furnished is proportional to voltage, not the square of voltage; this improves voltage stability on large networks. Synchronous condensers are often used in connection with high-voltage direct-current transmission projects or in large industrial plants such as steel mills.
For power factor correction of high-voltage power systems or large, fluctuating industrial loads, power electronic devices such as the static VAR compensator or STATCOM are increasingly used. These systems are able to compensate sudden changes of power factor much more rapidly than contactor-switched capacitor banks and, being solid-state, require less maintenance than synchronous condensers.
Non-linear loads
Examples of non-linear loads on a power system are rectifiers (such as used in a power supply), and arc discharge devices such as fluorescent lamps, electric welding machines, or arc furnaces. Because current in these systems is interrupted by a switching action, the current contains frequency components that are multiples of the power system frequency. Distortion power factor is a measure of how much the harmonic distortion of a load current decreases the average power transferred to the load.
Non-sinusoidal components
In linear circuits having only sinusoidal currents and voltages of one frequency, the power factor arises only from the difference in phase between the current and voltage. This is displacement power factor.
Non-linear loads change the shape of the current waveform from a sine wave to some other form. Non-linear loads create harmonic currents in addition to the original (fundamental frequency) AC current. This is of importance in practical power systems that contain non-linear loads such as rectifiers, some forms of electric lighting, electric arc furnaces, welding equipment, switched-mode power supplies, variable speed drives and other devices. Filters consisting of linear capacitors and inductors can prevent harmonic currents from entering the supplying system.
To measure the real power or reactive power, a wattmeter designed to work properly with non-sinusoidal currents must be used.
Distortion power factor
The distortion power factor is the distortion component associated with the harmonic voltages and currents present in the system.
is the total harmonic distortion of the load current.
is the fundamental component of the current, is the total current, and is the current on the h harmonic; all are root mean square values (distortion power factor can also be used to describe individual order harmonics, using the corresponding current in place of total current). This definition with respect to total harmonic distortion assumes that the voltage stays undistorted (sinusoidal, without harmonics). This simplification is often a good approximation for stiff voltage sources (not being affected by changes in load downstream in the distribution network). Total harmonic distortion of typical generators from current distortion in the network is on the order of 1–2%, which can have larger scale implications but can be ignored in common practice.
The result when multiplied with the displacement power factor is the overall, true power factor or just power factor (PF):
Distortion in three-phase networks
In practice, the local effects of distortion current on devices in a three-phase distribution network rely on the magnitude of certain order harmonics rather than the total harmonic distortion.
For example, the triplen, or zero-sequence, harmonics (3rd, 9th, 15th, etc.) have the property of being in-phase when compared line-to-line. In a delta-wye transformer, these harmonics can result in circulating currents in the delta windings and result in greater resistive heating. In a wye-configuration of a transformer, triplen harmonics will not create these currents, but they will result in a non-zero current in the neutral wire. This could overload the neutral wire in some cases and create error in kilowatt-hour metering systems and billing revenue. The presence of current harmonics in a transformer also result in larger eddy currents in the magnetic core of the transformer. Eddy current losses generally increase as the square of the frequency, lowering the transformer's efficiency, dissipating additional heat, and reducing its service life.
Negative-sequence harmonics (5th, 11th, 17th, etc.) combine 120 degrees out of phase, similarly to the fundamental harmonic but in a reversed sequence. In generators and motors, these currents produce magnetic fields which oppose the rotation of the shaft and sometimes result in damaging mechanical vibrations.
Power factor correction (PFC) in non-linear loads
Passive PFC
The simplest way to control the harmonic current is to use a filter that passes current only at line frequency (50 or 60 Hz). The filter consists of capacitors or inductors and makes a non-linear device look more like a linear load. An example of passive PFC is a valley-fill circuit.
A disadvantage of passive PFC is that it requires larger inductors or capacitors than an equivalent power active PFC circuit. Also, in practice, passive PFC is often less effective at improving the power factor.
Active PFC
Active PFC is the use of power electronics to change the waveform of current drawn by a load to improve the power factor. Some types of the active PFC are buck, boost, buck-boost and synchronous condenser. Active power factor correction can be single-stage or multi-stage.
In the case of a switched-mode power supply, a boost converter is inserted between the bridge rectifier and the main input capacitors. The boost converter attempts to maintain a constant voltage at its output while drawing a current that is always in phase with and at the same frequency as the line voltage. Another switched-mode converter inside the power supply produces the desired output voltage from the DC bus. This approach requires additional semiconductor switches and control electronics but permits cheaper and smaller passive components. It is frequently used in practice.
For a three-phase SMPS, the Vienna rectifier configuration may be used to substantially improve the power factor.
SMPSs with passive PFC can achieve power factor of about 0.7–0.75, SMPSs with active PFC, up to 0.99 power factor, while a SMPS without any power factor correction have a power factor of only about 0.55–0.65.
Due to their very wide input voltage range, many power supplies with active PFC can automatically adjust to operate on AC power from about 100 V (Japan) to 240 V (Europe). That feature is particularly welcome in power supplies for laptops.
Dynamic PFC
Dynamic power factor correction (DPFC), sometimes referred to as real-time power factor correction, is used for electrical stabilization in cases of rapid load changes (e.g. at large manufacturing sites). DPFC is useful when standard power factor correction would cause over or under correction. DPFC uses semiconductor switches, typically thyristors, to quickly connect and disconnect capacitors or inductors to improve power factor.
Importance in distribution systems
Power factors below 1.0 require a utility to generate more than the minimum volt-amperes necessary to supply the real power (watts). This increases generation and transmission costs. For example, if the load power factor were as low as 0.7, the apparent power would be 1.4 times the real power used by the load. Line current in the circuit would also be 1.4 times the current required at 1.0 power factor, so the losses in the circuit would be doubled (since they are proportional to the square of the current). Alternatively, all components of the system such as generators, conductors, transformers, and switchgear would be increased in size (and cost) to carry the extra current. When the power factor is close to unity, for the same kVA rating of the transformer more load current can be supplied.
Utilities typically charge additional costs to commercial customers who have a power factor below some limit, which is typically 0.9 to 0.95. Engineers are often interested in the power factor of a load as one of the factors that affect the efficiency of power transmission.
With the rising cost of energy and concerns over the efficient delivery of power, active PFC has become more common in consumer electronics. Current Energy Star guidelines for computers call for a power factor of ≥ 0.9 at 100% of rated output in the PC's power supply. According to a white paper authored by Intel and the U.S. Environmental Protection Agency, PCs with internal power supplies will require the use of active power factor correction to meet the ENERGY STAR 5.0 Program Requirements for Computers.
In Europe, EN 61000-3-2 requires power factor correction be incorporated into consumer products.
Small customers, such as households, are not usually charged for reactive power and so power factor metering equipment for such customers will not be installed.
Measurement techniques
The power factor in a single-phase circuit (or balanced three-phase circuit) can be measured with the wattmeter-ammeter-voltmeter method, where the power in watts is divided by the product of measured voltage and current. The power factor of a balanced polyphase circuit is the same as that of any phase. The power factor of an unbalanced polyphase circuit is not uniquely defined.
A direct reading power factor meter can be made with a moving coil meter of the electrodynamic type, carrying two perpendicular coils on the moving part of the instrument. The field of the instrument is energized by the circuit current flow. The two moving coils, A and B, are connected in parallel with the circuit load. One coil, A, will be connected through a resistor and the second coil, B, through an inductor, so that the current in coil B is delayed with respect to current in A. At unity power factor, the current in A is in phase with the circuit current, and coil A provides maximum torque, driving the instrument pointer toward the 1.0 mark on the scale. At zero power factor, the current in coil B is in phase with circuit current, and coil B provides torque to drive the pointer towards 0. At intermediate values of power factor, the torques provided by the two coils add and the pointer takes up intermediate positions.
Another electromechanical instrument is the polarized-vane type. In this instrument a stationary field coil produces a rotating magnetic field, just like a polyphase motor. The field coils are connected either directly to polyphase voltage sources or to a phase-shifting reactor if a single-phase application. A second stationary field coil, perpendicular to the voltage coils, carries a current proportional to current in one phase of the circuit. The moving system of the instrument consists of two vanes that are magnetized by the current coil. In operation, the moving vanes take up a physical angle equivalent to the electrical angle between the voltage source and the current source. This type of instrument can be made to register for currents in both directions, giving a four-quadrant display of power factor or phase angle.
Digital instruments exist that directly measure the time lag between voltage and current waveforms. Low-cost instruments of this type measure the peak of the waveforms. More sophisticated versions measure the peak of the fundamental harmonic only, thus giving a more accurate reading for phase angle on distorted waveforms. Calculating power factor from voltage and current phases is only accurate if both waveforms are sinusoidal.
Power Quality Analyzers, often referred to as Power Analyzers, make a digital recording of the voltage and current waveform (typically either one phase or three phase) and accurately calculate true power (watts), apparent power (VA) power factor, AC voltage, AC current, DC voltage, DC current, frequency, IEC61000-3-2/3-12 Harmonic measurement, IEC61000-3-3/3-11 flicker measurement, individual phase voltages in delta applications where there is no neutral line, total harmonic distortion, phase and amplitude of individual voltage or current harmonics, etc.
Mnemonics
Anglophone power engineering students are advised to remember: ELI the ICE man or ELI on ICE – the voltage E, leads the current I, in an inductor L. The current I leads the voltage E in a capacitor C.
Another common mnemonic is CIVIL – in a capacitor (C) the current (I) leads voltage (V), voltage (V) leads current (I) in an inductor (L).
References
- Das, J. C. (2015). Power System Harmonics and Passive Filter Design. Wiley, IEEE Press. p. 2. ISBN 978-1-118-86162-2.
To distinguish between linear and nonlinear loads, we may say that linear time-invariant loads are characterized so that an application of a sinusoidal voltage results in a sinusoidal flow of current.
- Boylestad, Robert (2002-03-04). Introductory Circuit Analysis (10th ed.). p. 857. ISBN 978-0-13-097417-4.
- "SI Units – Electricity and Magnetism". CH: International Electrotechnical Commission. Archived from the original on 2007-12-11. Retrieved 14 June 2013.
- The International System of Units (SI) [SI brochure] (PDF). § 5.3.2 (p. 132, 40 in the PDF file): BIPM. 2006. Archived (PDF) from the original on 2022-03-19.
{{cite book}}
: CS1 maint: location (link) - Authoritative Dictionary of Standards Terms (7th ed.), IEEE, 2000, ISBN 978-0-7381-2601-2, Std. 100
- Trial-Use Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions, IEEE, 2000, ISBN 978-0-7381-1963-2, Std. 1459–2000. Note 1, section 3.1.1.1, when defining the quantities for power factor, asserts that real power only flows to the load and can never be negative. As of 2013, one of the authors acknowledged that this note was incorrect, and is being revised for the next edition. See http://powerstandards.com/Shymanski/draft.pdf Archived 2016-03-04 at the Wayback Machine
- Suresh Kumar, K. S. (2013). Electric Circuit Analysis. Pearson. p. 8.10. ISBN 978-8-13-179155-4.
- Duddell, W. (1901), "On the resistance and electromotive forces of the electric arc", Philosophical Transactions of the Royal Society A: Mathematical, Physical and Engineering Sciences, 203 (359–371): 512–15, doi:10.1098/rsta.1904.0022,
The fact that the solid arc has, at low frequencies, a negative power factor, indicates that the arc is supplying power to the alternator…
- Zhang, S. (July 2006), "Analysis of some measurement issues in bushing power factor tests in the field", IEEE Transactions on Power Delivery, 21 (3): 1350–56, doi:10.1109/tpwrd.2006.874616, S2CID 39895367,
…(the measurement) gives both negative power factor and negative resistive current (power loss)
- Almarshoud, A. F.; et al. (2004), "Performance of Grid-Connected Induction Generator under Naturally Commutated AC Voltage Controller", Electric Power Components and Systems, 32 (7): 691–700, doi:10.1080/15325000490461064, S2CID 110279940,
Accordingly, the generator will consume active power from the grid, which leads to negative power factor.
- Ewald Fuchs; Mohammad A. S. Masoum (14 July 2015). Power Quality in Power Systems and Electrical Machines. Elsevier Science. pp. 432–. ISBN 978-0-12-800988-8.
The DPF is the cosine of the angle between these two quantities
- Sankaran, C. (1999), Effects of Harmonics on Power Systems, Electro-Test,
...and voltage-time relationship deviates from the pure sine function. The distortion at the point of generation is very small (about 1% to 2%), but nonetheless it exists.
- "Single-phase load harmonics vs. three-phase load harmonics" (PDF), Power System Harmonics, Pacific Gas and Electric, archived from the original (PDF) on 2015-09-24, retrieved 2013-11-26
- "Harmonic Effects" (PDF), Harmonics and IEEE 519, CA: EnergyLogix Solutions
- Sankaran, C. (1999), "Transformers", Effects of Harmonics on Power Systems, Electro-Test
- Sankaran, C. (1999), "Motors", Effects of Harmonics on Power Systems, Electro-Test,
The interaction between the positive and negative sequence magnetic fields and currents produces torsional oscillations of the motor shaft. These oscillations result in shaft vibrations.
- Schramm, Ben (Fall 2006), "Power Supply Design Principles: Techniques and Solutions, Part 3", Newsletter, Nuvation, archived from the original on 2007-03-09
- Wolfle, W.H.; Hurley, W.G. (2003), "Quasi-active power factor correction with a variable inductive filter: theory, design and practice", Xplore, vol. 18, no. 1, IEEE, pp. 248–255, Bibcode:2003ITPE...18..248W, doi:10.1109/TPEL.2002.807135
- Wölfle, W. H.; Hurley, W. G., "Quasi-active Power Factor Correction: The Role of Variable Inductance", Power electronics (project), IE: Nuigalway, archived from the original on 2020-08-06, retrieved 2008-11-05
- ATX Power Supply Units Roundup, xBit labs, archived from the original on 2008-11-20,
The power factor is the measure of reactive power. It is the ratio of active power to the total of active and reactive power. It is about 0.65 with an ordinary PSU, but PSUs with active PFC have a power factor of 0.97–0.99. hardware reviewers sometimes make no difference between the power factor and the efficiency factor. Although both these terms describe the effectiveness of a power supply, it is a gross mistake to confuse them. There is a very small effect from passive PFC – the power factor grows only from 0.65 to 0.7–0.75.
- The Active PFC Market is Expected to Grow at an Annually Rate of 12.3% Till 2011, Find articles, Mar 16, 2006, archived from the original on September 1, 2009,
Higher-powered products are also likely to use active PFC, since it would be the most cost effective way to bring products into compliance with the EN standard.
- Power Factor Correction, TECHarp,
Passive PFC the power factor is low at 60–80%. Active PFC ... a power factor of up to 95%
- Why we need PFC in PSU, Silverstone Technology, archived from the original on 2008-12-22,
Normally, the power factor value of electronic device without power factor correction is approximately 0.5. Passive PFC 70~80% Active PFC 90~99.9%
- Brooks, Tom (Mar 2004), "PFC options for power supplies", Taiyo, Electronic products, archived from the original on 2008-12-02,
The disadvantages of passive PFC techniques are that they typically yield a power factor of only 0.60 to 0.70 Dual-stage active PFC technology a power factor typically greater than 0.98
- Power Factor Correction (PFC) Basics (PDF) (application note), Fairchild Semiconductor, 2004, archived from the original (PDF) on 2014-06-11, retrieved 2009-11-29
- Sugawara, I.; Suzuki, Y.; Takeuchi, A.; Teshima, T. (19–23 Oct 1997), "Experimental studies on active and passive PFC circuits", INTELEC 97, 19th International Telecommunications Energy Conference, pp. 571–78, doi:10.1109/INTLEC.1997.646051, ISBN 978-0-7803-3996-5, S2CID 109885369
- Chavez, C.; Houdek, J. A. "Dynamic Harmonic Mitigation and power factor correction". EPQU'07. 9th International Conference Electrical Power Quality and Utilisation: October 9–11, 2007, Barcelona, Spain. IEEE. pp. 1–5. doi:10.1109/EPQU.2007.4424144. ISBN 978-84-690-9441-9.
- "Power Factor – Importance, Calculation and Correction techniques". 23 November 2018.
- Power Factor Correction Handbook (PDF), ON Semiconductor, 2007
- Program Requirements for Computers (PDF) (Version 5.0 ed.), US: Energy Star
- Bolioli, T.; Duggirala, M.; Haines, E.; Kolappan, R.; Wong, H. (2009), Version 5.0 System Implementation (PDF) (white paper), Energy Star, archived (PDF) from the original on 2022-10-09
- Fink, Donald G.; Beaty, H. Wayne (1978), Standard Handbook for Electrical Engineers (11 ed.), New York: McGraw-Hill, p. 3‐29 paragraph 80, ISBN 978-0-07-020974-9
- Manual of Electric Instruments Construction and Operating Principles, Schenectady, New York: General Electric, Meter and Instrument Department, 1949, pp. 66–68, GET-1087A
- "The Fundamentals of FFT-Based Signal Analysis and Measurement in LabVIEW and LabWindows/CVI". National Instruments Corporation. Retrieved 6 November 2017.
- "WT3000E Series Precision Power Analyzers" (PDF). Yokogawa Corporation. Archived from the original (PDF) on 7 November 2017. Retrieved 6 November 2017.
- "Fluke 1760 Three-Phase Power Quality Recorder" (PDF). Fluke Corporation. Archived (PDF) from the original on 2022-10-09. Retrieved 6 November 2017.
External links
- Harmonics and how they relate to power factor (PDF), U Texas, archived from the original (PDF) on 2011-09-27, retrieved 2010-09-20.