High-voltage transformer fire barriers

Article snapshot taken from Wikipedia with creative commons attribution-sharealike license. Give it a read and then ask your questions in the chat. We can research this topic together.
This article has multiple issues. Please help improve it or discuss these issues on the talk page. (Learn how and when to remove these messages)
This article needs additional citations for verification. Please help improve this article by adding citations to reliable sources. Unsourced material may be challenged and removed.
Find sources: "High-voltage transformer fire barriers" – news · newspapers · books · scholar · JSTOR (May 2018) (Learn how and when to remove this message)
Globe icon.The examples and perspective in this article may not represent a worldwide view of the subject. You may improve this article, discuss the issue on the talk page, or create a new article, as appropriate. (May 2018) (Learn how and when to remove this message)
(Learn how and when to remove this message)
High-voltage transformers with bushings on top, separated by a fire barrier

High-voltage transformer fire barriers, also known as transformer firewalls, transformer ballistic firewalls, or transformer blast walls, are outdoor countermeasures against a fire or explosion involving a single transformer from damaging adjacent transformers. These barriers compartmentalize transformer fires and explosions involving combustible transformer oil.

High-voltage transformer fire barriers are typically located in electrical substations, but may also be attached to buildings, such as valve halls or manufacturing plants with large electrical distribution systems, such as pulp and paper mills. Outdoor transformer fire barriers that are attached at least on one side to a building are referred to as wing walls.

Voluntary recommendations by NFPA 850

The primary North American document that deals with outdoor high-voltage transformer fire barriers is NFPA 850. NFPA 850 outlines that outdoor oil-insulated transformers should be separated from adjacent structures and from each other by firewalls, spatial separation, or other approved means for the purpose of limiting the damage and potential spread of fire from a transformer failure.

Automatic fire suppression systems

Instead of a passive barrier, fire protection water spray systems are sometimes used to cool a transformer to prevent damage if exposed to radiation heat transfer from a fire involving oil released from another transformer that has failed.

Transformer Fast Depressurization Systems (FDS)

Mechanical systems designed to quickly depressurize the transformer oil tank after the occurrence of an electrical fault can minimize the chance that a transformer tank will rupture given a minor fault, but are not effective on major internal faults.

Alternatives to mineral-based transformer oil

Transformer oil is available in with sufficiently low combustibility that a fire will not continue after an internal electrical fault. These fluids include those approved by FM Global. FM Data Sheet 5-4 indicates different levels of protection depending on the type of fluid used. Alternatives include, but are not limited to, esters and silicone oil.

See also

References

  1. "NFPA 850 Recommended Practice for Fire Protection for Electric Generating Plants and High-Voltage Direct Current Converter Stations". NFPA.org.
  2. FM Global Data Sheet 5-4 Transformers https://www.fmglobal.com/research-and-resources/fm-global-data-sheets
  3. NFPA 850
  4. Guide to Transformer Fire Safety Practices. cigre. June 2013. p. 80.
  5. Transformers and transformer fluids
  6. "Comparison of Silicone Oil and Mineral Oil Transformers". GlobeCore.com. Archived from the original on 2018-12-09. Retrieved 2018-12-12.
Categories: